18

Battery Run Times

ENVIRONMENTAL

Operating Temperature

0°C to +40°C (+32°F to + 104°F)

Storage Temperature

-15°C to +50°C (+5°F to + 122°F)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000 m (10,000 ft.) at 35°C (95°F) w/o derating

Audible Noise

< 40 dBA, at 1 meter

AGENCY

Safety

EN50091-1-1, TUV/GS listed, CE Compliance Mark

Surge

EN61000-4-5, Level 3, Criteria A

ESD

EN61000-4-2, Level 3, Criteria A

Susceptibility

EN61000-4-3, Level 2, Criteria A

Electrical Fast Transient/

Burst

EN61000-4-4, Level 3, Criteria A

Emissions

EN50091-2, Class B

Harmonics EN61000-3-2

Conducted Immunity

EN61000-4-6

Flicker EN61000-3-3

Transportation

ISTA Procedure 1A

Load %

500VA

650VA

5

95

117

10

53

73

20

25

35

30

19

20

40

12

12

50

8

8

60

7

7

70

5

4

80

3

3

90

3

2

100

2

1

Note: Approximate discharge times are in minutes and
at 25°C (77°F) with resistive load.