18
Battery Run Times
ENVIRONMENTAL
Operating Temperature
0°C to +40°C (+32°F to + 104°F)
Storage Temperature
-15°C to +50°C (+5°F to + 122°F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 35°C (95°F) w/o derating
Audible Noise
< 40 dBA, at 1 meter
AGENCY
Safety
EN50091-1-1, TUV/GS listed, CE Compliance Mark
Surge
EN61000-4-5, Level 3, Criteria A
ESD
EN61000-4-2, Level 3, Criteria A
Susceptibility
EN61000-4-3, Level 2, Criteria A
Electrical Fast Transient/
Burst
EN61000-4-4, Level 3, Criteria A
Emissions
EN50091-2, Class B
Harmonics EN61000-3-2
Conducted Immunity
EN61000-4-6
Flicker EN61000-3-3
Transportation
ISTA Procedure 1A
Load %
500VA
650VA
5
95
117
10
53
73
20
25
35
30
19
20
40
12
12
50
8
8
60
7
7
70
5
4
80
3
3
90
3
2
100
2
1
Note: Approximate discharge times are in minutes and
at 25°C (77°F) with resistive load.