MONITORING & COMMUNICATIONS


The UPStation® GX UPS is capable of communicating with a stand-alone computer
system, LAN server, UNIX host, or terminal via an EIA standard DB-25 female connector
located on the rear of the unit.

The UPS typically uses this capability to provide status and power monitoring information to
the computer system. For instance, during a power outage, the operating system uses
UPS information to automatically save information in buffers, close files, and shutdown
operations in an orderly fashion prior to exhausting the UPS battery.

Depending on your system configuration, the operating system may monitor power via the
UPS and control UPS operations using a variety of interface hardware. The UPS
communication interface port provides the signals and control pins required by monitoring
and control applications.

Connect the UPS and your computer system with the appropriate cable and SiteNet®1
shutdown software (sold separately). Consult your local Liebert representative to
determine the correct software kit for your application.

Intelligent Communications
Serial Communications Port -
Connection not to exceed NEC Class 2 limits. The DB-25
port provides several signals listed below by pin number:

PIN

FUNCTION

PIN

FUNCTION

1

Reserved

14

On Inverter

(active low)

2

RxD

15

On UPS

(active closed)

3

TxD

16

On battery

(active closed)

4

Not Used

17

Common

(for pins 15,16,18,24)

5

Not Used

18

On battery

(active open)

6

Not Used

19

UPS shutdown

(active high)

7

Signal ground

20

Not Used

8

Not Used

21

Low battery

(active low)

9

Low battery relay contact

(common)

22

Not Used

10

Low battery relay contact

(active opened)

23

Not Used

11

Low battery relay contact

(active closed)

24

On Bypass

(active closed)

12

Shutdown

(active low)

25

Altos specification tri-
voltage signal

13

Power failure

(active high)


In addition to power monitoring information signals, the UPS communicates intelligently
with LAN servers, UNIX hosts, or other connected computer systems. Optional SiteNet® 2
software allows these additional capabilities:

Quantitative monitoring of utility and UPS power

Quantitative monitoring of internal UPS parameters

Periodic tests of battery quality and replacement notification

Timed and delayed shutdown of the UPS

Logging of power disturbances and anomalies

Consult your Liebert sales agent for more information about SiteNet® 2 software.

SNMP Communications
An optional internal SNMP card (and SiteNet’ SNMP software) allows communication
through several network management systems. Call your Liebert supplier.