Battery run times, Upstation gxt battery run times, Internal battery (minutes) – Liebert 700-3000 VA User Manual

Page 21

Advertising
background image

21

UPSTATION GXT BATTERY RUN TIMES

(Discharge times are at 25° C ambient)

Internal Battery (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

52

94

94

169

78

160

101

20%

40

45

45

127

39

83

51

30%

32

33

33

94

27

47

28

40%

24

24

24

68

20

34

20

50%

18

18

18

49

15

27

15

60%

15

14

14

36

11

21

12

70%

12

12

12

28

9

18

10

80%

10

9

9

23

7

15

8

90%

8

7

7

19

6

13

7

100%

6

6

6

17

5

11

6

Internal Battery + 1 External Battery Cabinet (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

1500RT

2000RT

3000RT

10%

N/A

N/A

479

552

408

343

273

20%

N/A

N/A

255

335

215

204

140

30%

N/A

N/A

150

210

126

133

78

40%

N/A

N/A

110

152

95

100

57

50%

N/A

N/A

85

115

75

77

44

60%

N/A

N/A

66

88

57

60

35

70%

N/A

N/A

56

72

48

50

30

80%

N/A

N/A

48

62

40

43

26

90%

N/A

N/A

41

52

35

36

22

100%

N/A

N/A

35

45

29

31

18

Internal Battery + 2 External Battery Cabinets (minutes)

Load%

700MT

1000MT

1000RT

1000RTE

500RT

2000RT

3000RT

10%

N/A

N/A

848

920

718

623

444

20%

N/A

N/A

425

505

365

345

236

30%

N/A

N/A

243

303

208

211

138

40%

N/A

N/A

196

238

164

156

100

50%

N/A

N/A

168

198

139

120

75

60%

N/A

N/A

133

155

112

94

59

70%

N/A

N/A

109

125

94

81

50

80%

N/A

N/A

89

103

78

70

43

90%

N/A

N/A

77

88

68

62

36

100%

N/A

N/A

66

76

58

54

31