Specifications – Liebert 700-3000 VA User Manual

Page 26

Advertising
background image

26

SPECIFICATIONS

MODEL NUMBER

GXT1000RT-230

GXT1000RTE-230

MODEL RATING VA/W

1000 / 700

1000 / 700

DIMENSIONS: mm (in)
Unit
W x D x H

177 x 522 x 430

(7.0 x 19.3 x 16.9)

177 x 522 x 430

(7.0 x 19.3 x 16.9)

Shipping
W x D x H

340 x 660 x 565

(13.38 x 26.0 x 22.25)

340 x 660 x 565

(13.38 x 26.0 x 22.25)

WEIGHT: kg (lbs)
Unit

23.6 (51.9)

31.1 (68.4)

Shipping

26.8 (59.0)

34.3 (75.5)

INPUT AC PARAMETERS
Voltage Range (typical)

230 VAC nominal; variable based upon output load

100% - 70% Loading

160-163 VAC to 273-276 VAC

70% - 30% Loading

140-143 VAC to 273-276 VAC

30% - 0% Loading

120-122 VAC to 273-276 VAC

Frequency

48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing

Input connector

IEC320-10A

IEC320-10A

OUTPUT AC PARAMETERS
Output Sockets

(4) IEC320-10A

(4) IEC320-10A

Voltage

208/220/230/240 (switch selectable) VAC; ±3%

Frequency

50 Hz or 60Hz

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS
Type

Valve-regulated, nonspillable, lead acid

Qty. x Voltage x Rating

3 x 12V x 7 or 7.2 AH

6 x 12V x 7 AH

Back-up Time

See Typical Battery Discharge Curves

ENVIROMENTAL
Operating Temperature

0° C to +40° C (+32° F to +104° F)

Storage Temperature

-15° C to +50° C (+5° F to +122 °F)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000 m (10,000 ft.) at 40° C without derating

Storage Elevation

15.000 m (50,000 ft.) maximum

Audible Noise

<50 dBA, at 1 meter

AGENCY
Safety

EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant

RFI/EMI

EN55022, Class B; CE EMC Directive compliant

Immunity

IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC801-

5,Level 3

Advertising