Supervised alarm input configuration and wiring – Pelco DX2000 User Manual

Page 21

Advertising
background image

Pelco Manual C690M-E (11/04)

21

Supervised Alarm Input Configuration and Wiring

Supervised mode activates an alarm if the current in a line falls outside a specified range. This
blocks an attempt to defeat the alarm system by cutting a wire or through bypassing or
shorting a section of the circuit.

If the whole system is in supervised mode, then all inputs (including unused inputs) must be
terminated with 10K resistors (not included).

•

If you want the alarm contacts to be N.O., then wire the terminating resistor in parallel with
the alarm contacts.

•

If you want N.C., then wire the resistor in series.

Refer to Figure 7.

Figure 7. Supervised Alarm Input Wiring

1 2 3 4

SWITCH SETTINGS
SUPERVISED (NTSC)

NTSC/PAL

NOT USED

10K

ALM
UNIT

+V

GND

NO ALARM

NORMALLY CLOSED

10K

ALM
UNIT

+V

GND

NORMAL

ALARM CONDITION

10K

ALM
UNIT

+V

GND

ALARM CONDITION

CUT WIRE

10K

ALM
UNIT

+V

GND

NO ALARM

NORMALLY OPEN

10K

ALM
UNIT

+V

GND

NORMAL

ALARM CONDITION

10K

ALM
UNIT

+V

GND

ALARM CONDITION

CUT WIRE

SUPERVISED, NORMALLY OPEN

10K

10K

10K

10K

10K

10K

10K

10K

SUPERVISED, NORMALLY CLOSED

1
2

3
4

5
6

7
8

1
2

3
4

5
6

7
8

SUPERVISED, GROUP ALARM WIRING CONDITIONS

SUPERVISED MODE CONSIDERATIONS

INDIVIDUAL ALARM WIRING CONDITIONS

Advertising