PVI Industries SU-3 User Manual

Page 12

Advertising
background image

12

PV500-56 06/12

 

10.4 Burner Operation Record

Note: if any adjustments are made, it is important to recheck the manifold pressure and combustion
analysis. Check the following readings in the vent above the flue collector and below the barometric
damper.

BURNER OPERATION: Record the Readings at Steady State

Incoming Static Gas Pressure = “W.C. (kPa) (see burner data decal for range)

Incoming Flow Gas Pressure = “W.C. (kPa) (see burner data decal for range)

Manifold Gas Pressure = “W.C. (kPa) (see burner data decal for specified pressure)

CO2 % = (8% to 9.5% for Natural gas) (target 8.5%)

(9.5% to 10.5% for LP gas) (target 10.0%)

O2 % = (7.0% to 4.5%)

Carbon Monoxide (CO) in PPM = (should not exceed 200PPM) (target <100PPM)

NOx in PPM (If necessary)

Stack Temperature – Gross

0

F (300

0

F minimum, 500

0

F maximum)(149

0

C to 260

0

C)

Room Temperature

0

F (

0

C)

Draft (should be - 0.02 “W.C. to - 0.06 “W.C.)(- 0.005 kPa to - 0.015 kPa) (target - 0.04”
W.C.) (- 0.01 kPa)

High Gas Pressure Switch Setting (if equipped)

Low Gas Pressure Switch Setting (if equipped)

Head Setting Number

Air Shutter Setting Number

Running Motor Amps and Volts

Stored Water Temperature

0

F (

0

C)

Vent Diameter