PVI Industries SU-3 User Manual

Page 7

Advertising
background image

7

PV500-56 06/12

 

6.2 Gas Control Trains - All models include gas control trains with the following components: main manual

shutoff valve, two safety shutoff valves and pressure regulator. These components may be separate or two
or more may be combined in a common housing.

Caution: Do not adjust or remove any screws or bolts on gas train control components which are sealed
with a red or blue colored compound. Doing so will void all approvals and warranties.


6.3 Inlet Pressure -
Measure at the inlet pressure at the inlet pressure tap located on the upstream side (side

away from burner) on the top of the combination gas valve. The inlet pressure must remain within the
minimum and maximum values while the unit is at rest and while the unit is operating at maximum firing rate.






6.4 Manifold Pressure - Measure the manifold pressure at the manifold pressure tap located on top of the silver

elbow attached to the burner head. The rated manifold pressure appears on the burner data label located on
side of the burner control panel and is duplicated on the decal located near the front of the water heater.


6.5 Gas Service and Pipe Capacity - Before connecting the burner to the gas supply, insure that the gas pipes

and service meter are large enough to permit the additional load of the gas burner. (See Pipe Capacity
Table)

Pipe Capacity for Natural Gas Table*(x 1,000 Btu/h’s)

Pipe Length**

Nominal diameter of pipe in inches

1”

1 ¼”

1 ½”

2”

15’

345 750

30’

241 535 850

45’

199 435 700

60’

173 380 610

75’

155 345 545

90’

141 310 490

105’

131 285 450

920

120’

120 270 380

850

150’

109 242 300

780

180’

100 225 225

720

 

Using 0.6 Specific Gravity Gas and a Pressure Drop of 0.3” of Water Colum

 

   Multiplier for Propane: 1.57 

 

** Each 90

elbow counts as 3’ for the purpose of these calculations 

Pipe Capacity Example:

There is 75 feet of 1¼” pipe from the meter to the burner and there are 5 elbows.
(5 elbows X 3’) + 75’ pipe = 15’ + 75’ = 90’ of effective pipe length.
The maximum BTU that can be fired is 310,000 Btu/h. (See Pipe Capacity Table)

6.6 Gas Piping to Burner

All Piping Must Conform To Local Codes. Use black steel pipe and malleable iron fittings (do not use
cast iron parts
) with a suitable pipe dope which is resistant to liquefied petroleum gases.
 Safe operation of unit requires adequate gas supply with the required static and dynamic (flow)

pressures. Actual piping selection depends on many variables that must be carefully considered by the
gas piping system designer.

 Do not select gas pipe sizes based only on the supplied tables. These tables are for use by the gas piping

system designer as a reference in checking pipe size selections.

 The required gas pipe size may be larger than pipe connection size to the burner.

 It is advisable to run a separate gas line from the meter to the gas burner to avoid pressure drops.

 Installation of a union is suggested for ease of service.

 Install a manual main gas shutoff valve, as specified by Code, approximately 6 feet (1.8 m) away from

unit.

 A sediment trap (drip leg) MUST be provided in the inlet of the gas connection to the unit.

INLET PRESSURE

NAT. GAS

LP

Maximum Static Pressure (Inches-Water Column)

10.5" (2.62 kPa)

13" (3.24 kPa)

Minimum Flow Pressure (Inches-Water Column)

4.5" (1.21 kPa)

8" (1.99 kPa)

Advertising