Powerware Ferrups FE/QFE 500VA User Manual

Page 58

Advertising
background image

Internal Bypass Switch Installation

52

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

QFE: 50 Hz 220, 230, or 240 Vac Input and Output
FE: 60 Hz 220 Vac Input and Output
For FE 60 Hz 220 Vac, use only a BBM switch.

Figure 20. FE or QFE 4.3–18 kVA UPS with Internal Bypass Switch

Table 26. Input Current - Size Overcurrent Protection According To Local Code

Voltage

Charger

4.3 kVA

5.3 kVA

7 kVA

10 kVA

12.5 kVA

18 kVA

60 Hz

220 V

Standard

17A

21A

27A

41A

53A

81A

220 Vac

10A

18A

23A

28A

49A

60A

85A

20A

20A

25A

30A

52A

65A

89A

50 Hz

220 V

Standard

19A

21A

27A

43A

55A

81A

220 Vac

10A

22A

23A

28A

46A

58A

84A

20A

23A

25A

29A

51A

63A

89A

50 Hz

230 V

Standard

18A

20A

26A

41A

53A

78A

230 Vac

10A

20A

22A

27A

44A

56A

81A

20A

21A

24A

28A

49A

60A

85A

50 Hz

240 V

Standard

17A

19A

24A

39A

51A

75A

240 Vac

10A

19A

21A

26A

43A

54A

78A

20A

20A

23A

27A

47A

58A

82A

Advertising