8.0 Flue Options

Vertical
Flues

Y

X

Y

X

C

Roof

Terminal

A

B

This bend is equivalent to

1 metre

Total Equivalent Length =

A+B+C+1x90°Bend

All vertical and angled runs must be included,

measured from the boiler adaptor (point X) to the

joint with the flue terminal (point Y). One 91.5°

bend or two 135° bends can be included without

reduction of the flue length.

If further elbows are required the flue length must

be reduced by the following amounts:-

1 metre for each 91.5° bend

0.5 metre for each 135° bend

8.2

Vertical Flue Systems

1. Maximum permissible equivalent flue lengths are:-

(60/100)

(80/125)

Vertical Concentric

10 metres

20 metres

2. Any additional “in line” bends in the flue system must be
taken into consideration. Their equivalent lengths are:-
Concentric Pipes:

135° bend

0.5 metres

93° bend

1.0 metres

The elbow supplied with the standard horizontal flue kit is
not included in any equivalent length calculations

NOTE: Flue length is measured from point X to Y as
shown.

IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.