Powerware 9170+ User Manual

Page 56

Advertising
background image

UPS Startup

52

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

3. If you are installing power management software, connect your

computer to the UPS communication port using the supplied

communication cable.

DB-9 Connector for

Computer Cable

Figure 42. Communication Port

4. The UPS front panel display automatically turns on whenever

input power is present and at least one power module is

installed. Set up the initial operating parameters through the

front panel display (see



Initial Startup Parameters" on

page 56).

NOTE The unit has no physical On/Off switch. The UPS On/Off function must be

accessed through the front panel display.
NOTE If the UPS has been manually set to operate in Bypass or Battery mode, change

the System mode menu selection (menu 2) to Auto to return to normal Auto mode

operation.

5. Test proper operation of optional external control signals and

computer communication before connecting the load. (See

DB-9 Port Pin Functions" on page 71 for details.)

6. Plug the equipment to be protected into the UPS output

receptacles. Turn on the equipment that is connected to the

UPS.
DO NOT protect laser printers with the UPS because of the

exceptionally high power requirements of the heating elements.

NOTE The total volt-ampere load must not exceed the volt-ampere rating of the entire

cabinet. See Balancing Receptacle Loads" on page 58 for additional information.