The High Efficiency (H.E.) mode is a user-programmable automatic

mode of operation. This mode allows power to flow through the internal

UPS bypass path for as long as AC input stays within the user-defined

setpoints. If the input voltage or frequency deviates beyond these

setpoints, the Powerware 9170 system transfers to the Double

Conversion mode of operation. Complete loss of input voltage causes

the UPS to transfer to Battery mode. While in H.E. mode, the Powerware

9170 system provides passive EMI filtering in the power path.
Off mode turns off the output and most internal circuitry. Within this

mode, another mode (Sleep) turns off all internal circuitry when AC line

is not present and battery voltage drops to a low threshold. If AC input

voltage is not present in Off mode, the user can direct the UPS to enter

Sleep mode by selecting the Battery Protect (BP) feature. When AC

input voltage returns in the Off mode (caused by a low battery alarm

condition), the UPS automatically recovers and, if the Auto Restart

parameter is enabled, switches to Double Conversion. Auto Restart is

enabled as a factory-default.
The UPS will not automatically recover from the Sleep mode, regardless

of the state of the Auto Restart parameter.
Figure 46 shows the basic functional elements of the UPS.

Input

(Utility)

Power

Input Power (Boost)

Converter

Internal DC

Power Bus

DC/AC Power Inverter

Output Relay

Bypass Relay

Capacitor Bank

Battery Charger

Battery

Modules

(Parallel)

Line/Battery

Relay

Isolation

Transformer

(Optional)

EMI/RFI

Filter

Figure 46. Powerware 9170 UPS Functional Block Diagram