Safety controls, Vacuum air pressure (fan) switch, Water pressure switch – Pentair MiniMax NT LN User Manual

Page 22: Thermal fuse, Low gas pressure switch

Advertising
background image

P/N 472089

Rev. E 4-19-05

22

SAFETY CONTROLS

VACUUM AIR PRESSURE (FAN) SWITCH

The air pressure switch, (see

Figure 20

), is a safety device

used to insure that the combustion air blower (fan) is
operating and has been designed to monitor the vacuum
(negative) pressure within the blower housing. The air
pressures switch is factory set and is connected upstream
of the ignition module. The ignition module does not
operate unless the air pressure switch and all safety switches
are closed.

WATER PRESSURE SWITCH

The water pressure switch, (see

Figure 21

), closes when

there is a sufficient flow of water to the heat exchanger to
safely operate the heater. The switch has been preset by
the Factory at 1½ PSI for operation. NOTE: See, Below
Pool Level Installation instructions on

page 8

. The switch

may remain closed with no water flow if there is more
than a 3 ft. elevation difference between the heater (heat
exchanger) and the pool water line—if this is the case, the
water pressure switch must be reset by a qualified service
technician to maintain open switch contacts with no water
flow.

NOTE

If the pool is more than one floor above or one floor
below the heater, the water pressure switch may
have to be replaced with a flow switch.

THERMAL FUSE

This is a single-use switch, mounted on combustion
chamber jacket divider (inner front panel). The fuse, (see

Figure 22

), is activated by excessive temperature due to

abnormal operating conditions. Upon detection of
excessive heat within the inner front panel, the fuse will
open the safety circuit causing shutdown of the heater.

LOW GAS PRESSURE SWITCH

The MiniMax NT LN model heater uses a low gas supply
pressure switch, (see

Figure 23

), ahead of the gas valve, to

prevent operation of the heater when the gas supply
pressure is below the minimum required for proper
operation of the burners. The switch is factory set. In the
event that the switch does not close and prevents the firing
of the heater, the cause of the low gas supply pressure must
be corrected. Typical causes are undersized supply piping,
undersized gas meter or low gas regulator setting (gas
supply regulator and gas meter problems are typically
corrected by your local gas company).

Typical Water Pressure Switch

AIR PRESSURE SWITCH

Figure 20.

Air Pressure Switch

Thermal Fuse