Table 8. Troubleshooting Guide (continued)

Alarm or Condition

Possible Cause

Action

1 beep

The UPS is running on

Correct the input voltage, if possible. The UPS

every 2

battery power because the

continues to operate on battery until the condition is

seconds

input voltage is too high or

corrected or the battery is completely discharged.

too low.

If the condition persists, the input voltage in your area
may differ from the UPS nominal.

1 beep per

Power requirements exceed

The UPS will automatically shut down in 3 minutes.

second

UPS capacity (overload is

Save your work immediately and turn off your

greater than 120%) or the

equipment. Turn off the UPS.

load is defective.

Remove some of the equipment from your UPS. You.
may need to obtain a larger capacity UPS.

1 beep per

The UPS is on battery and

Shutdown is imminent (30 seconds). Save your work

second

the power requirements

and turn off your equipment. Turn off the UPS.

exceed UPS capacity

Remove some of the equipment from the UPS. You

(overload is greater than

may need to obtain a larger capacity UPS.

120%) or the load is
defective.

Continuous

Battery test failed.

Check the battery connections and be sure the

beep

battery is fully charged.

If the

indicator still flashes, see “UPS

Maintenance” on page 15 to replace the battery. Call
your service representative if the problem persists

Continuous

UPS internal temperature is

Shutdown is imminent. Save your work and turn off

beep

too high.

your equipment. Turn off the UPS.
Clear vents and remove any heat sources. Wait at
least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.

Continuous

UPS fan fault (750-1400VA

Save your work and turn off your equipment. Turn off

beep

models only)

the UPS. Contact your service representative.