The ENVIROMUX-DCVD-xxx can also be connected to the “RJ45 SENSORS” sockets on the ENVIROMUX-SEMS-16. When
using a CAT5 patch cable to make connection, you must first determine what wiring standard the cable has been made to. Make
connections based on the chart below.

TERMINAL ON
ENVIROMUX-DCVD-xxx

RJ45 Socket

Pin #

Cable Wire Color

(T568A Standard)

Cable Wire color

( T568B Standard)

+

1

Green Orange


2

Green/White Orange/White

















Wire connections for ENVIROMUX-SEMS-16 using RJ45 Sensor sockets

ENVIROMUX-DCVD-24V

+

1 2 3 4 5 6 7 8

View looking into RJ45 Socket

Using a patch cable from NTI (wired to the T568B
Standard), Orange/White is at postion 1, and Orange
is at position 2 in the RJ45 connector.

Using a cable wired to the T568A Standard,
Green/White is at postion 1, and Green
is at position 2 in the RJ45 connector.

White

Green

Black

+

( )

( )

( )

REAR VIEW OF ENVIROMUX-SEMS-16