Attention, Model 155ecm, Performance – Lifebreath MAXTOP User Manual

Page 7: Engineering data, Dimensions 155ecm

Advertising
background image

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

7

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
High effficiency electronic comutated ECM motor for maximum energy sav-
ings. Each air stream has one centrifugal blower. 5 speed fan operation
driven by one double shaft motor. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation. Drain connections 2 -
1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40
Recirculation mode, Recirculation mode (each mode has 5 speeds). Control
pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)

BALANCING DAMPER

33 5/8"

(850mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19" (483)

*All Duct Connections 6" (150mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front clearance of 25 inches (635 mm)
is recommended for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150 mm)

99-186

Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen

99-SILENCER6 6” dia. 16” long

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.

DIMENSIONS 155ECM

inches (mm)

Model 155ECM

All units conform to CSA
and UL standards.

The ECM motor produces a tone that some may
find objectionable. We recommend the
installation of the optional 99-SILENCER6 on the
‘Stale Air from Inside’ and ‘Fresh Air to Inside’
ducts.

ATTENTION

*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

164 (77)

@ 0.2" (50 Pa)

157 (74)

@ 0.3" (75 Pa)

147 (69)

@ 0.4" (100 Pa)

146 (69)

@ 0.5" (125 Pa)

140 (66)

@ 0.6" (150 Pa)

138 (65)

@ 0.7" (175 Pa)

131 (62)

@ 0.8" (200 Pa)

121 (57)

Max. Temperature Recovery

79%

Sensible Effectiveness
@ 66 cfm (31 L/s)

32°F (0°C)

72%

*Sensible Efficiency
@ 66 cfm (31 L/s)

32°F (0°C)

66%

*Sensible Efficiency
@ 66 cfm (31 L/s)

-13°F (-25°C)

67%

VAC @ 60HZ

120

WATTS / Low speed.

17

WATTS / High speed

95

Amp rating

1.4

5

1

2

3

4

10

30

50

70

90

110

130

150

170

190

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

A

ir

Fl

ow

(

c

fm

)

5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data

Advertising