759 mm (29 7/8")

200 mm

(8")

FRONT VIEW

625 mm

(24 5/8 ")

1055 mm

(41 1/2")

508 mm

(20")

172 mm

(6 3/4")

INLET SIDE

DRAIN CONNECTION

DIMENSIONS 1200DDPOOL

mm (inches)

200 mm

(8")

1055 mm

(41 1/2")

508 mm

(20")

159 mm

(5 7/8")

MOUNTING POINTS

CONTROLS

DISCHARGE SIDE

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM POOL

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 760 mm (30 in.)
from front
access doors

POOL AND

DEFROST AIR

263 mm

(10 3/8")

263 mm

(10 3/8")

All units conform to CSA and UL standards.

WARRANTY
Units carry a 15 year warranty on the heat recovery cores
and a 2 year replacement parts warranty.

AIRFLOWS (Each Air Stream)

613 (1300)

566 (1200)

518 (1100)

472 (1000)

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)

EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

7.8 MED

8.1 HIGH

7.1 LOW

70%

60%

50%

235

(500)

282

(600)

329

(700)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

EFFECTIVENESS

HIGH SPEED

HIGH SPEED

MED SPEED

MED SPEED

LOW SPEED

LOW SPEED

378

(800)

423

(900)

472

(1000)

566

(1200)

518

(1100)

NOTE: Exhaust Relative Humidity (RH) at 40%

PERFORMANCE

Model 1200DD POOL

TI -121

1203

SPECIFICATIONS

CORES
Modular (3 section) patented aluminum heat recovery cores arranged
for efficient cross-flow ventilation. Meets the flame spread and smoke
developed classifications of the National Building Code and NFPA 90A
(1993 Edition).

MOTORS
Two PSC, 3 speed double shafted, 120 VAC, 4 Amps each (8.1 total
on high speed). HP - 1/4, 1625 RPM. Watts - total on high speed -
972.

FILTERS
Washable air filters in exhaust and supply air streams.

BLOWERS
Centrifugal type rated at 1200 cfm (566 L/s) free air delivery. Each air
stream has one double shafted motor driving a centrifugal blower.

CONNECTION DUCT SIZES
Five - 20" x 8" H (508 mm x 200 mm H).

MOUNTING
Unit to be set on support brackets hung by threaded rod type
apparatus. (brackets and rods not provided).

CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated with foil faced insulation duct liner where required
to prevent exterior condensation. Drain connections; two - 1/2" (12
mm) O.D.

CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC)
terminals for connection of remote dehumidistat (supplied) and defrost
light indicating automatic operation.

DEFROST CONTROLS
Supply bypass damper routes indoor air to defrost core.

WEIGHT 191 lbs. (87 kg) SHIPPING WEIGHT 215 lbs. (98 kg)

DATE: ___________________________________________PROJECT: _________________________________________

MECHANICAL CONTRACTOR: _________________________________________________________________________

4