SPECIFICATIONS

CORES

Modular (3 section) patented aluminum heat recovery cores arranged for
high efficiency cross-flow ventilation. Meets the flame spread and smoke
developed classifications of the National Building Code and NFPA 90A (1993
Edition).

MOTORS

Two PSC, 3 speed double shafted, 120 VAC, 3.95 Amps each (7.9 total on
high speed). HP - 1/4, 1625 RPM. Watts - total on high speed - 848.

FILTERS Washable air filters in exhaust and supply air streams.

BLOWERS

Each air stream has one double shafted motor driving 2 centrifugal blowers.

HYDRONIC REHEAT COIL

Standard built-in coil in both 1000RHC and 1000RHCAC. Rated 35,000 BTU

@ 140°F, 3 US gal./min. Design temperature drop is 20°F, fluid pressure drop
is 1.3 feet WG at rated flow, 3/4" fittings.

CONNECTION DUCT SIZES

Five - 20" X 8" H (508 mm x 200 mm H).

DIRECT EXPANSION (DX) EVAPORATOR COIL (model 1000RHCAC
only)

Factory installed 1.5 ton DX coil, 0.875" OD suction side, 0.625" OD

liquid side, built-in orifice.

MOUNTING

Two brackets under cabinet, connect to threaded rod type supports
(not included).

CASE

20 gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated with foil faced insulation where required to prevent exterior conden-
sation. Drain connections; two - 1/2" (12 mm) O.D.

CONTROLS

Illuminated power switch, 3 speed blower control, low voltage (24 VAC) termi-
nals to connect remote controls (not included), defrost light indicating
defrost/recirculation mode.

DEFROST CONTROLS

Supply bypass damper routes indoor air to defrost core.

WEIGHT

255 lbs.(116 Kg)

SHIPPING WEIGHT

280 lbs.(127 Kg)

1088 mm

(46 3/4")

200 mm

(8")

FRONT VIEW

1055 mm

(41 1/2")

508 mm

(20")

DISCHARGE SIDE

625 mm

(24 5/8")

INLET SIDE

DRAIN CONNECTION

COIL FITTINGS

508 mm

(20 ")

DIMENSIONS 1000RHC/RHCAC

mm (inches)

DEFROST &

RECIRCULATION

AIR

EXHAUST AIR

TO OUTSIDE

SUPPLY AIR

TO BUILDING

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 760 mm (30 in.)

508 mm

(20 ")

CONTROLS

149 mm

(5 7/8 ")

263 mm

(10 3/8 ")

263 mm

(10 3/8 ")

99-101

Sixty Minute Remote Timer

99-130

Remote Wall Mount Dehumidistat Control
24VAC only

All units conform to CSA and UL standards.

WARRANTY
Units carry a 15 year warranty on the heat recovery cores and
a 2 year replacement parts warranty.

TI-115

1203

AIRFLOWS (Each Air Stream)

613 (1300)

566 (1200)

518 (1100)

472 (1000)

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7) 200 (.8)

EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

7.8 MED

8.1 HIGH

7.1 LOW

70%

60%

50%

235

(500)

282

(600)

329

(700)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

NOTE: Exhaust Relative Humidity (RH) at 40%

EFFECTIVENESS

HIGH SPEED

HIGH SPEED

378

(800)

423

(900)

472

(1000)

566

(1200)

518

(1100)

PERFORMANCE

Performance data includes both reheat and DX coil installed.

Note there is little change in air flow with the DX coil removed.

Model 1000RHC and

Model 1000RHCAC

NOTE:

Hydronic reheat coil is designed to temper the ventilation air (after heat recovery) back to room temperature, and is not
intended for use as a primary heating source for the space.

Additional controls MUST be added to pump system (not included / not available from Nutech) feeding the coil to ensure
continuous water flow through it, and prevent freezing of the coil.

DX coil is designed to reduce humidity brought in from outside during ventilation. Coil MUST be connected to an outdoor
condensing unit (not included) by certified trades person. Not intended as a primary air conditioning system for the space.

DATE:_____________________________________________PROJECT: ________________________________________

MECHANICAL CONTRACTOR: __________________________________________________________________________

5

Advertising
This manual is related to the following products: