Nordyne Outdoor Heat Pump Two Stage Split System R-410A User Manual

Page 17

Advertising
background image

17

Status

LED

Status LED

Description

Status LED Troubleshooting Information

Green

“POWER”

Module has
power

Supply voltage is present at module terminals

Red “TRIP”

Thermostat
demand signal
Y is present, but
compressor is not
running

Compressor protector is open

Check for high head pressure

Check compressor supply voltage

Outdoor unit power disconnect is open

Compressor circuit breaker or fuse(s) is open

Broken wire or connector is not making contact

Low pressure switch open if present in system

Compressor contactor has failed open

Yellow “ALERT”

Flash Code 1

Long Run Time
Compressor is
running extremely
long run cycles

Low refrigerant charge

Evaporator blower is not running

Check blower relay coil and contacts

Check blower motor capacitor

Check blower motor for failure or blockage

Check evaporator blower wiring and connectors

Check indoor blower control board

Check thermostat wiring for open circuit

Evaporator coil is frozen

Check for low suction pressure

Check for excessively low thermostat setting

Check evaporator airfl ow (coil blockages or return airfi lter)

Check ductwork or registers for blockage

Faulty metering device

Check TXV bulb installation (size, location and contact)

Check if TXV/fi xed orifi ce is stuck closed or defective

Condenser coil is dirty

Liquid line restriction (fi lter drier blocked if present in system)

Thermostat is malfunctioning

Solenoid plug not connected

Y2 not wired at Comfort Alert

Check thermostat sub-base or wiring for short circuit

Check thermostat installation (location, level)

Comfort Alert failure

Yellow “ALERT”

Flash Code 2

System Pressure
Trip

High head pressure

Check high pressure switch if present in system

Check if system is overcharged with refrigerant

Check for non-condensable in system

Discharge or
suction

Condenser coil poor air circulation (dirty, blocked, damaged)

pressure out of
limits

Condenser fan is not running

Check fan capacitor

Check fan wiring and connectors

Check fan motor for failure or blockage

compressor
overloaded

Return air duct has substantial leakage

If low pressure switch present in system, check Flash Code
1 information

TROUBLESHOOTING

Table 4. LED Diagnostics