Caution – Nordyne Outdoor Heat Pump Two Stage Split System R-410A User Manual

Page 9

Advertising
background image

9

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

Ampacity

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

Table 1. Copper Wire Size

• Connect the line-voltage leads to the

terminals on the contactor inside the control
compartment.

• Use only copper wire for the line voltage power

supply to this unit (Table 1). Use proper code
agency listed conduit and a conduit connector
for connecting the supply wires to the unit.
Use of rain tight conduit is recommended.

• See the unit wiring label for proper high and low

voltage wiring. Make all electrical connections
in accordance with all applicable codes and
ordinances.

• Use a separate branch electrical circuit for this

unit. A means of electrical disconnect must be
located within sight of and readily accessible
to the unit. This switch shall be capable of
electrically de-energizing the outdoor unit.

• Overcurrent protection must be provided at the

branch circuit distribution panel and sized as
shown on the unit rating label and according
to applicable local codes.

Outdoor Unit Connections
The outdoor unit requires both power and control
circuit electrical connections. Refer to the unit
wiring diagram / schematic for identifi cation and
location of outdoor unit fi eld wiring interfaces.

Control Circuit Wiring
The outdoor unit is designed to operate from a
24 VAC Class II control circuit. The control circuit
wiring must comply with the current provisions
of the NEC (ANSI/NFPA 70) and with applicable
local codes having jurisdiction.

Thermostat Connections
Thermostat connections should be made in
accordance with the instructions supplied with
the thermostat, and with the instructions supplied
with the indoor equipment. A typical residential
installation with a heat pump thermostat and air
handler are shown in Figure 2.

Figure 2. Typical 2 - Stage Heat Pump w/

Optional Outdoor Thermostat and Variable

Speed Air Handler

G R W2 C E O Y1

Thermostat

OD

Stat

O Y1

R

C

Air Handler

Heat Pump OD Section

W 2

E

W2

W1

O

Y/Y2

G

R

C

Y2

Y2

W1 W3

Y1

NOTE: Jumper

W1 & W2 together
for shorter staging

time.

Grounding

CAUTION:

The unit must have an uninterrupted or
unbroken electrical ground to minimize
personal injury if an electrical fault
should occur. This ground may consist of
electrical wire or approved conduit when
installed in accordance with national or
local codes.

Low-Pressure Switch
A low-pressure switch is factory installed and
located internally on the suction line of the
outdoor unit. The switch is designed to protect the
compressor from a loss of charge by interrupting
the thermostat inputs to the unit.

If the suction pressure falls below 5 psig, the
switch will open and de-energize the outdoor
unit. The switch will close again when the suction
pressure increases above 20 psig. NOTE: When
the switch opens and then closes, there is a 3
minute short cycling delay before the outdoor
unit will energize. Under normal conditions the
switch is closed.

High-Pressure Switch
A high-pressure switch is factory installed and
located internally on the compressor discharge
line of the outdoor unit. If the discharge pressure
rises above 650 psig, the switch will open and
de-energize the outdoor unit. The switch will close

Advertising