Specification

Media Box Efficiency max.

85% and 95%

Maximum Face Velocity over Media

750 fpm (3.8 m/s)

Maximum Face Velocity with Integral Mist Eliminator

1080 fpm (5.5 m/s)

Pressure Drop at 500 fpm

0.25 IWC (62 Pa)

Fire Protection Rating

UL 900 Class I

Power supply pump (REflow, REflow C, REflow SC)

120 VAC/1, 50 and 60 Hz

Power consumption

0.2 - 0.6 kw

Water supply pressure

30 - 145 psi

Unit Height

26” (650mm) - 130” (3300mm)

Unit Width

24” (610mm) - 130” (3300mm)

Unit Depth

30” (575mm)

Standards and guidelines

UL 900 Class 1 and NRTL Approval

INSTallaTION fEaTURES & REqUIREMENTS

Pre-assembled hydraulic package for quick installation

Only three connections to be made- water, drain and electrical

REflow pump model powered by a 120 V 1phase 60Hz connection

Stainless steel water tank and lateral supports

Media boxes can be installed in seconds

Footprint not to exceed 3” top and 2” side clearance from AHU/duct wall

pERfORMaNCE

0

0.35

0.70

1.05

1.40

100

200

300

400

500

600

700

800

900 1000 1100

Nortec MH Pressure Drop

Pressure Drop (lWC)

Face Velocity (fpm)

Media 8 inch depth

Media 12 inch depth

Mist Eliminator 4 inch depth (necessary for velocity > 748 fpm)

Mist Eliminator 8 inch depth (necessary for velocity > 885 fpm)

50

60

70

80

90

100

100

200

300

400

500

600

700

800

900 1000 1100

Nortec MH Humidification Efficiency

Efficiency (%)

Face Velocity (fpm)

Media 8 inch depth

Media 12 inch depth