REDUCTION OF CLEARANCES TO PROTECTED
SURFACES

CLEARANCES

CLEARANCES FROM COMBUSTIBLE SURFACES

(All dimensions are in inches)

Note: The boiler shall be installed in a space large in
comparison to the size of the boiler. Large space is
defined as having a volume at least sixteen (16) times
the total volume of the boiler.

Note 1:
Combustible floor shield is required when boiler is to be
installed on a combustible surface. (See ordering infor-
mation on pg. 4.)

Note 2:
Servicing Clearances: Provide at least 24" (Models
133-1826), 48" (Models 2100-4001) in front of unit for
removal and servicing of the Controls & Burner Tray.
Provide at least 18" on side opposite water connections
for deliming of Heat Exchanger Tubes.

*Vent includes factory-supplied drafthood and does not
include field-supplied vent systems above the draft-
hood. On Models 2100-4001 drafthood is built into
boiler.

6

Derived from National Fuel Gas Code, Table 6.2.3(a)

Derived from National Fuel Gas Code, Table 6.2.3(b)

MODEL

133

181 to

401

514 to

824

926 to

1826

2100 to

4001