Control screens – Raypak Y-200 User Manual

Page 13

Advertising
background image

13

Control Screens

To access programming mode: Press and hold the
"MODE" button for 4 seconds. When in Program
mode, cursor is blinking on first settable parameter.
UP/DOWN arrows change parameter. LEFT/RIGHT
arrows move to next selectable parameter.

Table D: Control Screens

NOTE: Once programming is finished, go to

Screen 28 to program the USER DEFAULT
SET_UP. Then open the front panel and press
the SW3 reset button on the motherboard to save
the new programming.

SCREEN

DESCRIPTION

FACTORY DEFAULT

Initial Screen

01 Displays the product identification and version of software.

None

Calendar, Time,

Initial Setpoint

02

The present month, day, year and time in a 24-hour clock
format; setpoint temperature.

None

°F or °C

02

Temperature can be displayed in degrees Fahrenheit or
Celsius.

Default Value = °F

Setpoint

02

40 to 220°F (4.4 to 104.4°C); the system output temperature
desired when the outdoor temperature is 70°F (21.1°C); or in
domestic hot water applications, the desired water temperature.

Default = 140°F

(60°C)

Control Band

03

1 to 10°F; the temperature above and below the Target
Temperature at which the boiler turns off and on. NOTE: The
Control Band is disabled in PID operation. If the Control Band is
adjusted during PID operation, it disables the PID function.

Default = 3°F

No value when in PID

Offset

04

Degrees of offset added to or subtracted from the initial
setpoint at the date and time selected.

Default = OFF

Setting Holiday 05 Data from screen 04 is combined with these screen settings.

Default = 00-00-RH

Reset Ratio

06

None (for Domestic Hot Water Application ONLY) or 0.01:1 to 8:1;
determines how much the internally-calculated Target
Temperature will change for a given outdoor temperature change.

Default value =

200°F@10°F

(93.3°[email protected]°C)

System Status

07 Shows the status of the system.

None

Water

Temperature

Limits

08

Maximum "USER" water temperatures 235°F (112.7°C) and
Minimum water temperatures 40°F (4.4°C) Display Only.

Max default value =

180°F / 82.2°C

Min default value =

105°F / 40.5°C

Changes: Screen 23

Outdoor Cutoff

Temperature

09

32 to 200°F (0 to 93.3°C), a warm-weather shutdown feature.
When the outdoor temperature exceeds this setting, the boiler
will not fire unless placed in manual override mode.

Default value = 75°F

(23.8°C)

Outdoor Cutoff

Deadband

10

-01 to -10°F; the number of degrees below the Outdoor
Cutoff Temperature which causes the Outdoor Cutoff
Temperature to reset.

Default value = -3°F

System/Network

Monitor

11

Displays the Pump, Boiler, Stage and Auxiliary contact
status. If flashing, contacts are closed (ON).

This screen is

DISPLAY only.

Outdoor Water

TAR

12

Displays the current Outdoor Air, System Water and Target
Temperature in degrees °F or °C.

Default = °F

AUX Delay

13

000 to 600 seconds; determines when the pump shuts off
after entering Outdoor Cut-off mode.

Default = 180 seconds

Boiler/Stage On

Delay

14

0 to 600 seconds; sets the time interval between sequential
boiler start-ups. 0 to 600 seconds; sets time interval
between stages turning on.

Default = 10 seconds

Disabled in PID