Communication (RS485) Wiring

Required for Optional Slave

Unit(s)

Y-304 Slave Cable Installation from

System Control module

•

Y-304 slave cable or equivalent shielded commu-
nications cable (Belden #9842, Belden #8132 or
Alpha 3492C) must be used. Maximum cable
length 100 ft. Correct polarity must be observed.
Make use of wire color coding to ensure polarity.

•

The shielding [foil wrapper-bare wire (drain)]
MUST be grounded. Grounding is done at the
Master Y-200 Control only. DO NOT ground the
shield at the slave unit end of the cable.

•

Note: Equivalent shielded cable must be suitable
for RS485 communication applications; must have
100-140 ohm impedance and less than 30 pico-
farad per foot capacitance.

•

Must be installed in conduit that does not contain
any other wiring.

•

Port J18 (see Fig. 4) is used for the interconnec-
tion between the master controller and slave units.

•

Master/Slave interconnection should be wired
from Master to Slave #1, Slave #1 to Slave #2,
Slave #2 to Slave #3, and Slave #3 to Slave #4.

Air Temperature Sensor

Installation

•

Locate the sensor on the coldest side of building,
usually the north side.

•

Install the sensor in a shaded area, out of direct
sunlight.

•

Locate no higher than 2/3 way up the side of the
building, or between the 2nd and 3rd floor if the
building is more than 3 stories tall.

•

Do not locate under an overhang, near wall cor-
ners, near drafts from stacks, air moving devices,
windows, doors, or balconies.

•

Shielded twisted pair (18 AWG) must be used for
sensor connections. Polarity must be observed.
Cable length shall not exceed 300 feet, and the
shielding must be grounded.

•

Grounding is done at the Master Y-200 control
ONLY. Do Not ground the Slave units or
Temperature Sensor enclosure.

•

Must be installed with properly-sized conduit that
contains no other wiring.

•

The outdoor air temperature and water tempera-
ture sensor are identical and interchangeable.

Fig. 4: Master RS485 Communications Cable

Schematic