11.4.2 To Turn Heater Off
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
To restart, turn the thermostat above room
temperature.

11.5 Simple Troubleshooting
Some possible reasons for the heater not operating
are:

1. Gas supply not "ON".

2. Electricity supply not "ON".

3. The time and/or temperature controls are not

"ON".

4. A limit switch may have operated. This may be

caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.

If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.

11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.
Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction. See Page 27, Figure 16 for LED
indication codes.

Figure 16: LED Diagnostic Codes

LED INDICATION FAULT MODE

Slow Flash

Normal Operation - No call for heat.

Fast Flash

Normal Operation - Call for heat.

2 Flashes

Ignition Lockout - No flame detected.

3 Flashes

Airflow Fault - Pressure switch open or closed.

4 Flashes

Temperature Limit or
Manual Reset Limit Switch Open

5 Flashes

Flame Sense Error - Gas valve not energized.

Steady On

Internal Control Failure