Warning, Typical suspension details – Roberts Gorden VANTAGE NP CTHN-125 User Manual

Page 16

Advertising
background image

CTHN-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

10

SECTION 7: GENERAL SUSPENSION DETAILS

To ensure your safety and comply with the terms of
the warranty, all units must be installed in
accordance with these instructions.

The gas or the electrical supply lines must not be
used to support the heater.

Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.

The heater must be installed in a location that is
readily accessible for servicing.

The heaters must be installed in accordance with
clearances to combustibles as indicated on the rating
plate and in this instruction manual.

The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating
plate.Typical installation configurations are shown in
Figure 12.

FIGURE 12: Critical Hanger Placement

WARNING

Suspension Hazard

Burner is secured to burner tube

by bolts and lockwashers.

Hang heater with materials

with a minimum working

load of 75 lbs (33 kg).

Failure of the supports

can result in death, injury

or property damage.

Hanger

Side View

Must Be Within 4" (10 cm)

Front View

S-hooks

Reflector

Hanger

45° Angle

* Allows for thermal expansion of system

Typical Suspension Details

Rod 3/8"

Beam Clamp

Concrete Beam

Wood Beam

Washers

Locknut

Screw Hook

3/8"

24" min.*

(61 cm)

“X”*

Anchor

S-hooks

Chain Size

3/16"

Minimum

Turnbuckle

Not Included

Description

Part Number

S-Hook

91907302

Tube/Reflector Hanger

03090100

Run Length

Typical Expansion

Minimum “X” Length

10' (3 m) - 50' (15 m)

±1" (3 cm)

12" (30 cm)

51' (15.5 m) - 60' (18 m)

±2" (5 cm)

18" (46 cm)

61' (18.6 m) - 80' (24 m)

±3" (8 cm)

24" (61 cm)

Advertising