15. Replace thermostat cover by snapping into place.

16. Turn on power to system. Test thermostat as described in the

following section.

Step 3: Testing the Thermostat

WARNING:

DO NOT SHORT (JUMPER) ACROSS TERMINALS
OF GAS VALVE OR SYSTEM CONTROL TO TEST
OPERATION. THIS WILL DAMAGE THE
THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: DO NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE

IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR
CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.

1. Place the EMER-HEAT-OFF-COOL switch into

the COOL position. The display will read COOL.

2. Press the

ٚ

button until the temperature setting

is at least 3 degrees below the room temperature.

The air conditioning system should turn on within

a few seconds. The snowflake icon

will be displayed

( 1

st

stage cooling; 2

nd

stage cooling).

6

TERMINAL LEGEND - 9420

TERM

EQUIPMENT TO CONNECT

REQ?

TERMINAL FUNCTION

C

24VAC common connection

Yes

For input of 24VAC common
side of transformer

L

System fault indicator connection

No

For connection of system
fault indicator (if present)

R

24VAC hot connection

Yes

For input of 24VAC hot side
of transformer

Y2

Second stage cooling connection

No

Energizes on a call for
second stage cooling

Y1

First stage compressor connection

Yes

Energizes on a call for
first stage of heating and
cooling

E

Emergency heat connection

No*

Energizes on a call for heat
in the EM mode only

G

Indoor fan connection

Yes

Energizes with E, Y1, Y2 and
W2 terminals or with FAN
option switched to the ON
position

W2

Second stage heat connection

No*

Energizes on a call for
second stage of heat
(auxiliary heat)

O

Cool active reversing

Yes**

Energizes when in the in

valve connection

COOL mode

B

Heat active reversing

Yes**

Energizes when in the

valve connection

HEAT or EM modes

*

For systems using a backup heat source. If separate E terminal connection is not available,
jumper E and W2.

** Most heat pump systems will have a cool active or a heat active reversing valve. Use the

appropriate terminal.

!