Caution – Roberts Gorden VANTAGE NP CTHN-200 User Manual

Page 9

Advertising
background image

SECTION 2: I

NSTALLER

R

ESPONSIBILITY

3

SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:

• To install the heater, as well as the gas and

electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon
recommends the installer contact a local Building
Inspector or Fire Marshal for guidance.

• To use the information given in a layout drawing

and in the manual together with the cited codes
and regulations to perform the installation.

• To install the heater in accordance with the

clearances to combustibles requirements.

• To furnish all needed materials not furnished as

standard equipment.

• To plan location of supports.
• To provide access to burners on all sides for

burner servicing and removal.

• To provide the owner with a copy of this

Installation, Operation and Service Manual.

• To never use heater as a support for a ladder or

other access equipment and never hang or
suspend anything from heater.

• To ensure there is adequate air circulation around

the heater and to supply air for combustion,
ventilation and distribution in accordance with
local codes.

• To safely and adequately install heater using

materials with a minimal working load of 75 lbs
(33 kg).

• To ensure the heater is placed in an approved

application.

2.1 Wall Tag

A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Roberts-Gordon or
your ROBERTS GORDON

®

independent distributor

to obtain the wall tag. Affix the tag by peeling off the
backing of the adhesive strips on the rear surface
and position the tag on a wall near the heater (e.g.
thermostat or ROBERTS GORDON

®

Controller).

A copy of the wall tag (P/N 91037912) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the burner and in the Installation, Operation and
Service Manual. See Page 4, Figure 3 through Page
7, Figure 12
. Write the proper clearance dimensions
in permanent ink according to your model number
and configuration in the open spaces on the tag.

2.2 Corrosive Chemicals

Roberts-Gordon cannot be responsible for ensuring
that all appropriate safety measures are undertaken
prior to installation; this is entirely the responsibility of
the installer. It is essential that the contractor, the
sub-contractor, or the owner identifies the presence
of combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
premises.

* Halogenated Hydrocarbons are a family of
chemical compounds characterized by the
presence of halogen elements (fluorine, chlorine,
bromine, etc.). These compounds are frequently
used in refrigerants, cleaning agents, solvents, etc.
If these compounds enter the air supply of the
burner, the life span of the heater components will
be greatly reduced. An outside air supply must be
provided to the burners whenever the presence of
these compounds is suspected. Warranty will be
invalid if the heater is exposed to halogenated
hydrocarbons.

2.3 National Standards and Applicable Codes

All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.

CAUTION

Product Damage Hazard

Do not use heater in area containing
corrosive chemicals.

Refer to appropriate Material Safety Data
Sheets (MSDS).

Failure to follow these instructions can result
in product damage.

Advertising
This manual is related to the following products: