Ieee 1613 type tests, Iec environmental type tests, Agency approvals – RuggedCom RS416 User Manual
Page 42: 3 iec environmental type tests

Type Tests
42
RuggedCom
®
RuggedServer™ RS416 Family Installation Guide rev118
7.2 IEEE 1613 Type Tests
IEEE Test
IEEE
1613
Clause
Description
Test Levels
C37.90.3
9
ESD
Enclosure Contact
+/- 8kV
Enclosure Air
+/- 15kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
C37.90.1
7
Fast Transient
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
Earth ground ports
+/- 4kV
C37.90.1
7
Oscillatory
Signal ports
2.5kV common mode @ 1MHz
D.C. Power ports
2.5kV common & differential mode @ 1MHz
A.C. Power ports
2.5kV common & differential mode @ 1MHz
C37.90
6
H.V. Impulse
Signal ports
5 kV (Failsafe Relay)
D.C. Power ports
5 kV
A.C. Power ports
5 kV
C37.90
6
Dielectric
Strength
Signal ports
2kVAC
D.C. Power ports
1.5kVDC
A.C. Power ports
2kVAC
Table 25 - IEEE 1613 Type Tests
Notes:
If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During
disturbance, errors may occur but recovery is automatic).
If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During
disturbance, no errors will occur).
7.3 IEC Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 60068-2-1
Cold
Temperature
Test Ad
-40 deg. C, 16 Hours
N/A
IEC 60068-2-2
Dry Heat
Test Bd
+85 deg. C, 16 Hours
N/A
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing), 55°C, 6
cycles
N/A
IEC 60255-21-1
Vibration
2g @ (10-150) Hz
Class 2
IEC 60255-21-2
Shock
30g @ 11 ms
Class 2
Table 26 - Environmental Type Tests