Ordering information, Temperature control units, High-speed counter unit – Omron CPU Unit CJ2 User Manual

Page 34: Position control units

Advertising
background image

34

Temperature Control Units

■

Unit

classification

Product

name

Specifications

No. of

unit

numbers

allocated

Current

consumption

(A)

Model

Standards

No. of loops

Temperature

sensor inputs

Control outputs

5 V

24 V

CJ Special
I/O units

Temperature
Control Units

4 loops

Thermocouple
input (R, S, K, J,
T, B, L)

Open collector NPN
outputs (pulses)

2

0.25

—

CJ1W-TC001

UC1, N, L,
CE

4 loops

Open collector PNP
outputs (pulses)

0.25

—

CJ1W-TC002

2 loops, heater
burnout detection
function

Open collector NPN
outputs (pulses)

0.25

—

CJ1W-TC003

2 loops, heater
burnout detection
function

Open collector PNP
outputs (pulses)

0.25

—

CJ1W-TC004

4 loops

Platinum
resistance
thermometer input
(JPt100, Pt100)

Open collector NPN
outputs (pulses)

0.25

—

CJ1W-TC101

4 loops

Open collector PNP
outputs (pulses)

0.25

—

CJ1W-TC102

2 loops, heater
burnout detection
function

Open collector NPN
outputs (pulses)

0.25

—

CJ1W-TC103

2 loops, heater
burnout detection
function

Open collector PNP
outputs (pulses)

0.25

—

CJ1W-TC104

High-speed Counter Unit

■

Unit

classification

Product

name

Specifications

No. of

unit

numbers

allocated

Current

consumption

(A)

Model

Standards

Countable

channels

Encoder A and B inputs,

pulse input Z signals

Max.

counting

rate

5 V

24 V

CJ Special
I/O units

High-speed
Counter Unit

2

Open collector
Input voltage: 5 VDC, 12 V, or 24 V
(5 V and 12 V are each for one
axis only.)

50 kcps

4

0.28

—

CJ1W-CT021

UC1, N, L,
CE

RS-422 line driver

500 kcps

Position Control Units

■

Unit

classification

Product

name

Specifications

No. of

unit

numbers

allocated

Current

consumption

(A)

Model

Standards

No. of

axea

Control output interface

5 V

24 V

CJ Special
I/O units

Position
Control
Units

1 axis

Pulse train, open collector output

1

0.25

—

CJ1W-NC113

UC1, CE

2 axes

Pulse train, open collector output

0.25

—

CJ1W-NC213

4 axes

Pulse train, open collector output (See note.)

2

0.36

—

CJ1W-NC413

1 axis

Pulse train, line driver output

1

0.25

—

CJ1W-NC133

2 axes

Pulse train, line driver output

0.25

—

CJ1W-NC233

4 axes

Pulse train, line driver output (See note.)

2

0.36

—

CJ1W-NC433

Space Unit

Use a CJ1W-SP001 Space Unit if the operating temperature is 0 to 55

°C.

CJ1W-SP001

UC1, CE

Note: The ambient operating temperature for 4-Axis Position Control Units is 0 to 50°C; the allowable voltage fluctuation on the external 24-VDC power supply is 22.8 to 25.2 VDC (24 V ±5%).

Ordering Information

Advertising