CPU unit component descriptions

1. DIP switch

RS-232C and peripheral port settings

Operating mode at startup

Pin 2 determines the operating mode at startup only if there isn't a
programming device connected to the peripheral port.

2. Input indicators (yellow)

The input indicators are lit when the corresponding
input terminal is ON. The status of an input indicator
will reflect the status of the input even when that input
is being used for a high-speed counter.

Note: 1.

When interrupt inputs are used in interrupt input mode, the in-
dicator may not light even when the interrupt condition is met
if the input is not ON long enough.

2.

Input indicators will reflect the status of the corresponding in-
puts even when the PLC is stopped, but the corresponding in-
put bits will not be refreshed.

3.

Output indicators (yellow)

The output indicators are lit when the corresponding output terminal is
ON. The indicators are lit during I/O refreshing. The status of an output
indicator will also reflect the status of the corresponding output when
the output is being used as a pulse output.

4.

High-speed counter indicators (yellow)

The indicators are lit when the corresponding input
terminal is ON.

5.

PLC status indicators

The following indicators show the operating status of the PLC.

Operation

7. Communications switch

6. Communications port

8. DeviceNet port

9. RS-422/485 port

10. Terminating resistance switch

11. CompoBus/S port

12. Digital I/O and
encoder interface

13. FE connection

1. DIP switch

16. DeviceNet

node address

14. Battery

15. Low battery detection switch

17. DeviceNet indicators
18. CompoBus/S indicators

5. PLC status indicators

4. High-speed counter indicators
3. Output indicators
2. Input indicators

Pin 1

Effective port settings

OFF
(default)

The ports operate according to the settings in the
PLC setup.
RS-232C port settings: DM 6645 to DM 6649
Peripheral port settings: DM 6650 to DM 6654

ON

The ports operate with the standard communications
settings.

Programming device
connected

Startup mode with
Pin 2 OFF (default)

Startup mode with
Pin 2 ON

None

RUN mode

PROGRAM mode

Programming console

Operating mode set on the programming console's
mode switch

Other device

PROGRAM mode

1 2 3 4

ON

OUT0

OUT1

OUT2

OUT3

IN0

IN1

IN2

IN3

IN4

IN5

Indicator

Status

Meaning

PWR
(green)

ON

Power is being supplied to the unit

OFF

Power isn't being supplied to the unit

RUN
(green)

ON

The PLC is operating in RUN or
MONITOR mode

OFF

The PLC is in PROGRAM mode or
a fatal error has occurred.

ERR/ALM
(red)

ON

A fatal error has occurred.
(PLC operation stops.)

Flashing

A non-fatal error has occurred.
(PLC operation continues.)

OFF

Indicates normal operation.

COMM1
(yellow)

Flashing

Data is being transferred via the
peripheral or RS-422/485 port.

OFF

Data isn't being transferred via
communications port.

COMM2
(yellow)

Flashing

Data is being transferred via the
RS-232C port

OFF

Data isn't being transferred via
communications port.

A

B

Z

PWR

RUN

ERR/ALM

COMM1

COMM2