2 sg burner setup – Quincy Compressor Air Compressor User Manual

Page 15

Advertising
background image

3.2 SG Burner Setup

Boiler Model

SG-2

SG-3

SG-4

Burner Model

BF-3

BF-5

BF-5

Firing Rate

0.65

1.00

1.30

Insertion Depth

5.0"

5.0"

5.0"

Nozzle

.55 X 70

.85 X 60

1.10 X 80

Spray Pattern

solid

solid

solid

Pump Pressure

145 psi

145 psi

145 psi

Turbulator

0

0

2

Air Gate

4.5

4.0

5.6

BURNER MANUFACTURER Riello
BF3 and BF5

BURNER MANUFACTURER

Heat Wise

Pioneer

Boiler Model

SG-2

SG-3

SG-4

Burner Model

P-1 FV

P-1 KA

P-2 KA

Firing Rate

.65

1.00

1.30

Insertion Depth

3.5”

3.5”

3.5”

Nozzle

0.5 X 80

0.75 X 70

1.00 X 80

Spray Pattern

solid

solid

Semi Solid

Pump Pressure

200

200

200

Head Setting

6

3

3

Air Setting

12.0

11.5

11.5

12

Boiler Model

SG-2*

SG-3*

SG-4*

Burner Model

NEC - 1201

NEC - 1202

NEC - 1202

Firing Rate

0.65

1.00

1.30

Insertion Depth

3.5”

6.0”

6.0”

Nozzle

.50 X 60

o

.75 X 60

o

1.00 X 60

o

Spray Pattern

hollow

solid

solid

Pump Pressure

180 psi

180 psi

180 psi

Head Type

6 slot

9 slot

9 slot

Head Position

1.50

3.50

4.25

BURNER MANUFACTURER

Beckett

NX (NEC 1201, 1202)

* - These burners may not be used in Canada on Biasi equipment

Advertising