TDK GENESYS 750W HALF RACK User Manual

Page 38

Advertising
background image

83-507-5002 Rev. B

30

Table 4-2: Rear panel Connections and Controls (continued)

Number

Item

Description

Section

4

Remote Out
connector

RJ-45 type connector, used for daisy-chaining power supplies to
form a serial communication bus.

7.3
7.5

5

J1 Analog
Remote
connector

Connector for remote analog interface. Includes Output Voltage
and Current programming and monitoring signals, Shut-off control
(electrical signal), Enable/Disable control (dry-contact), Power Sup-
ply OK (PS_OK) signal and operation mode (CV/CC) signal.

4.5

6

SW1 Setup
switch

Nine position DIP-switch for selecting remote programming and
monitoring modes for Output Voltage, Output Current and other
control functions.

4.4

7

J2 Remote
sense
connector

Connector for making remote sensing connections to the load for
regulation of the load voltage and compensation of load wire drop.

3.10
3.8.2

8

Blank
Sub-plate

Blank sub-plate for standard units. Isolated Remote Analog pro-
gramming connector for units equipped with Isolated Analog control
option. IEEE connector for units equipped with IEEE programming
option (shown).

Fig. 4.2

9

IEEE switch

Two position DIP-switch for selecting IEEE mode or RS232/RS485
mode when IEEE option is installed.

Fig. 4.2

10

Ground
screw

M4x0.7, 8mm long DBL-SEMS screw for chassis ground
connection.

Fig. 4.2

4.4 REAR PANEL SW1 SETUP SWITCH

The SW1 Setup switch (see Fig.4-3) is a 9-position DIP-switch that allows the user to choose the
following:

−

Internal or remote programming for Output Voltage and Output Current.

−

Remote voltage or resistive programming of Output Voltage and Output Current limit.

−

Select range of remote voltage and resistive programming.

−

Select range of output Voltage and Output Current monitoring.

−

Select the Remote Shut-Off control logic.

−

Select between RS232 and RS485 communication interface.

−

Enable or disable the rear panel Enable/Disable control (dry contact).

4.4.1 SW1 position function
Refer to Table 4-3 for description of SW1 position functions. The factory default setting is
Down for all positions.

Fig.4-3: SW1 setup DIP-switch

1

2

3

4

5

6

7

8

9