3-4. 208-240 VAC CHARGER AND AC TO DC CONVERTER LIMITS

The unit is designed with a single point AC receptacle for external

power to operate both the internal charger and converter. The units

AC voltage range can be factory set from 208 to 240 VAC SINGLE PHASE

30 AMPS MAX at 50/60 Hz depending upon customer requirements. The AC

power cord provided with the unit is the mechanism that ensures the

specified AC power source is properly supplied to the unit (see para-

graph 3-5). Use no others

INTERNAL CHARGER: NO LIMIT AC power cord can remain connected

when power cells are fully charged. When the power cells are fully

charged the unit’s intelligent charger will go to a standby mode,

monitor the power cells state of charge, and only charge the power

cells to ensure they stay at maximum capacity.

INTERNAL AC TO DC CONVERTER: LIMITED (see paragraph 3-6, 3-8 and

3-10). AC power cord does not have to be disconnected when con-

verter power output is no longer required. Once DC power demand

is terminated the unit’s intelligent charger will remain on line to

ensure power cells are charged to maximum capacity.

CAUTION

Unit will be damaged if unapproved AC power is applied.

3-5 AC POWER CORD LIMITS

The AC power cord governs which AC power source the unit is set to

operate from. The Turbo Start 4100 is supplied with a single cus-

tomer specified AC power cord.

3-2