11.6 Grounding configuration

This section describes the grounding configuration with AC input service entrance.

As inadequate grounding configuration causes problems on start-up, connections for the ground line

and the neutral line must be done properly according to the system configuration.

11.6.1 Recommended configuration with input neutral grounded

Figure 11.8 shows recommended grounding configuration with input neutral grounded.

The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should

be open, as the neutral line must be grounded only at one point in a system. And the neutral line must

be properly fed to the bypass input.

Figure 11.8 - Grounding configuration with input neutral grounded.

A jumper cable of 2AWG (or 38mm

2

) is provided between the neutral terminal and ground bus in the

UPS cabinet. Notice that the electrical contractor should unscrew and disconnect the jumper cable in

this configuration. The cable location is illustrated below.

Figure 11.9 - Jumper cable between the neutral terminal & ground bus.

N

G

3

φ

3

φ

3

φ

N

G

< UPS Cabinet >

N

3

φ

3

φ

G

Input Source

Disconnect
The Cable

Ground

Bus

Neutral

Terminal

Disconnect

Jumper

Cable here

< 100~225kVA >

Ground

Bus

Disconnect

Jumper

Cable here

< 250/300kVA >

Neutral

Terminal

G

N

3

φ

To the
Load