Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP User Manual

Page 30

Advertising
background image

22

1600Xp Series installation and operation manual

STANDARD MODELS: 14 – 22 KVA

Capacity

14 kVA (11.9 kW)

1

18 kVA (15.3 kW)

1

22 kVA (18.7 kW)

1, 5

general
topology

true on-line

Certifications

AnSi C62.41 (ieee 587), Ul 1778, CUl, Ce, FCC Class A , neC (nFpS-70),

nemA/pe1-1993, oSHA, ASme, iSo 9001, iSo 14001:2004 , roHS Compliant

input Characteristics
input Voltage

1

Single-phase, 208/240 VAC, +10% to –30%

1

1

input Frequency

45-65 Hz (auto-sensing)

input Capacity

14 kVA

18 kVA

22 kVA

input /(max input) Current @208V

67.2 (68.9) A

86.4 (88.1) A

106 (107) A

input /(max input) Current @240V

58.2 (59.7) A

74.9 (76.3) A

92.0 (93.0) A

input power Factor

0.98 typical, 0.95 minimum@ 100% load

1

Current tHd (linear load)

< 5%

internal AC input breaker rating

100 A / 277 V

125 A / 277 V

battery Characteristics
battery type

Valve regulated lead Acid, Flame retardant

backup time, fully charged @ 0.7

power factor, 77 F

7 min.

2

5 min.

2

backup time, fully charged @ 0.85

power factor, 77 F

7 min.

2

5 min.

2

3 min.

2

recharge time

24hr. (full), 12hr.(90%) for internal batteries only

3

battery Voltage (nominal)

288 VdC

output Characteristics
output Voltage

Single-phase, 240/208/120 volts

output Voltage regulation

= ±3%

output Frequency

±0.5Hz/1.0Hz/1.5Hz (factory/authorized service center selectable only)

AUto/mAn Frequency

Factory or authorized service center selectable only

Voltage tHd

< 3% for linear load; < 6% for non-linear load

Common-mode noise

< .5 Vrms

rated load power Factor

1

0.85 (0.6 - 1.0) lagging

Efficiency (AC-DC-AC)

>86%

4

Voltage transient

< ±8% (load of 0 to 100 %)

Voltage transient recovery

50 ms to within 2% of nominal

rated output Current (rms)

58 A

75 A

91.6 A

max peak output Current

174 A

225 A

275 A

inverter overload Capacity

125%-30 sec./150%-10 sec

bypass overload Capacity

125%-10 min./1000%-1 cycle

Crest Factor

3.0

Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid

1.

when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.

battery

2.

backup time may vary depending on the operating conditions and ambient temperature at the installation site.

An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.

3.

Subject to update without notice.

4.

derate to 18.7 kVA (15.9 kw) for 50 Hz operation.

5.

Advertising