G9000 Installation and Operation Manual

77

Failure Code List

Table 6.1 Fault Code

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay contact

Failure

lamp

UA801

AC INPUT VOLTAGE

OUT OF RANGE

Input line voltage is out of the specified

range.

CHECK INPUT

POWER

SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA802

AC INPUT

FREQUENCY OUT

OF RANGE

Input line frequency is out of the specified

range.

CHECK INPUT

POWER

SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA803

AC INPUT PHASE

ROTATION ERROR

Input line power conductors are not wired in

a proper phase sequence.

CHECK INPUT

POWER

SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA804

CONVERTER OPE.

PROHIBITED

The converter interlock is active.

Intermittent

sound

Alarm

UA805

INVERTER

OVERLOAD

The output load current has exceeded 105%

of the rated current.

WARNING :

DECREASE

LOAD

Intermittent

sound

Alarm

Overload

UA806

INVERTER

OVERLOAD

The output load current has exceeded 110%

of the rated current.

WARNING :

DECREASE

LOAD

Intermittent

sound

Alarm

Overload

UA807

INVERTER

OVERLOAD

The output load current has exceeded 125%

of the rated current.

WARNING :

DECREASE

LOAD

Intermittent

sound

Alarm

Overload

UA808

INVERTER

OVERLOAD

The output load current has exceeded 150%

of the rated current.

WARNING :

DECREASE

LOAD

Intermittent

sound

Alarm

Overload

UA810

INVERTER

OVERLOAD

Short time over-current has been detected

during the inverter operation.

WARNING :

DECREASE

LOAD

Intermittent

sound

Alarm

Overload

UA812

BYPASS VOLTAGE

OUT OF RANGE

Bypass line voltage is out of the specified

range.

CHECK BYPASS

INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA813

BYPASS PHASE

ROTATION ERROR

Bypass line power conductors are not wired

in a proper phase sequence.

CHECK BYPASS

INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA814

BYPASS

FREQUENCY OUT

OF RANGE

Bypass line frequency is out of the specified

range.

CHECK BYPASS

INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA815

TRANSFER

PROHIBITED

Transfer to the bypass is not available due to

bypass abnormality.

Intermittent

sound

Alarm

UA817

EMERGENCY STOP

ACTIVATED

The emergency stop was activated by the

EPO switch or an external contact.

Alarm

UA821

TRANSFER

PROHIBITED

The UPS could not transfer to the bypass

because the inverter output was not

synchronized to the bypass.

Alarm

UA822

TRANSFER

PROHIBITED

The UPS could not transfer to the bypass

because external “generator operation”

signal indicates a backup generator is in

operation.

Alarm