Installation, Special lifting and moving instructions, Ƽƽ c ca au ut tiio on n – Trane RTUB 207-224 User Manual

Page 10: Ƽƽ w wa ar rn niin ng g, Isolation, Foundation

Advertising
background image

10

Special Lifting and Moving
Instructions

A specific lifting method is
recommended as follows:

1. Four lifting points are built into the

unit.

2. Slings and spreader bar to be

provided by rigger and attached to
the four lifting points.

3. Minimum rated lifting capacity

(vertical) of each sling and
spreader bar shall be no less than
the tabulated unit shipping weight.

ƽ

ƽ C

CA

AU

UT

TIIO

ON

N

This unit must be lifted with the
utmost care. Avoid shock load by
lifting slowly and evenly.

ƽ

ƽ W

WA

AR

RN

NIIN

NG

G

To prevent any damage, position the
lifting bar so that the slings do not
touch the unit.

Isolation

The most effective form of isolation
is to locate the unit away from any
sound-sensitive area. Structurally
transmitted sound can be reduced by
elastomeric vibration eliminators.
Spring isolators are not
recommended for units equipped
with helical rotary compressors.
Consult an acoustical engineer in
critical sound applications. For
maximum isolation effect, isolate
water lines and electrical conduit.
Wall sleeves and rubber- isolated
piping hangers can be used to
reduce the sound transmitted
through water piping. To reduce the
sound transmitted through electrical

conduit, use flexible electrical
conduit. State and local codes on
sound emissions should always be
considered.

Foundation

Provide rigid, non-warping mounting
pads or a concrete foundation of
sufficient strength and mass to
support the unit's operating weight
(that is, including completed piping,
and full operating charges of
refrigerant, oil, and water). After it is
in place, the unit must be level
within 1/4" [6 mm] over its length
and width. Use shims if necessary.
The manufacturer is not responsible
for equipment problems resulting
from an improperly designed or
constructed foundation.
Note for RTCA: The unit must be
positioned so that the airflow
through the condensation coils is not
hindered by any obstacle. The

Installation

Figure 2- Rigging the unit - RTUB 207-208

Figure 3- Rigging the unit - RTUB 210-224

Figure 4- Rigging the unit - RTCA 108-216

Table 3 - Sling Lengths (mm) for lifting

A

B

C

D

E

RTUB unit size
207-208

2200

3000

2600

2100

-

210-211-212

2400

3000

2550

3150

3650

214-216-217

2500

3000

2550

3150

3650

218-220

2450

3050

2600

3150

3650

222-224

2450

3100

2650

3150

3650

RTCA unit size
108/109/111/208/209/211

2240

1700

1700

-

-

113/115/115/213/215/216

2240

2800

2800

-

-

RLC-SVX03A-E4