Installation, Clearances – Trane RTUB 207-224 User Manual

Page 11

Advertising
background image

11

Installation

condensation coils must be
protected from side winds when
their speed exceeds 16 km/h.
Position the unit above the average
height of snow observed in the
region where it is installed. Never
install temporary or permanent
objects (tarp or roof) over the unit,
because recycling of hot air would
reduce the capacity of the
condensation coils. Discharged air
from the fans must not be
obstructed. It is prohibited to install
ducts for the fan discharge air (even
short ones). This is because the fans
supplied on standard units do not
generate any additional static
pressure.

Clearances

Provide enough space around the
unit to allow the installation and
maintenance personnel unrestricted
access to all service points. Refer to
Figure 5 and Table 4 for unit

Figure 5: Unit Dimensions and
Recommended Minimum
Clearances - RTCA

Figure 6: Unit Dimensions and
Recommended Minimum
Clearances - RTUB

A

C

D

B

A

C

D

B

Table 4 - Unit Dimensions and Recommended Minimum Clearances (mm)

Length

Width

Height

A

B

C

D

RTCA 108/109/111/208/209/211

2870

2285

1630

1000

1000

1000

1000

RTCA 113/213

4610

2285

1630

1000

1000

1000

1000

RTCA 115/116/215/216

5450

2285

1630

1000

1000

1000

1000

RTUB 207/208

2880

890

1789

950

800

1800

500

RTUB 210/211/212/214/216/217

4150

890

1832

950

800

2750

500

RTUB 218/220

4150

890

1932

950

800

2750

500

RTUB 222/224

4150

890

2041

950

800

2750

500

dimensions and recommended
clearances. Unobstructed flow of
condenser air is essential to maintain
chiller capacity and operating
efficiency.

Note for RTCA: When determining
unit placement, give careful
consideration to ensuring a sufficient
flow of air across the condenser
heat-transfer surface.

RLC-SVX03A-E4