Performance data – Trane WSC060-120 User Manual

Page 31

Advertising
background image

PKGP-PRC004-EN

31

Performance
Data

Table PD-22 - Static Pressure Drops Through Accessories - (Pascals)

Econimizer with

Electric Heater

OA/RA Dampers

2

Accessory (kW)

3

Unit

Airflow

Standard

Pleated Filters

100% OA

100% RA

100% OA

100% RA

7-9

10-27

37-40

Model No.

(m

3

/h)

Filters

1

50 mm (2 inch)

Downflow

Horizontal

2720

25

37

30

11

30

4

11

13

—

WSC060AD,T

3400

37

55

46

17

46

6

17

21

—

4080

55

72

64

26

64

9

25

30

—

3260

10

17

25

2

15

5

—

5

—

WSC072AD,T

4080

15

22

27

5

20

5

—

8

—

4890

22

30

33

10

25

10

—

13

—

4080

15

22

27

5

20

5

—

8

—

WSC090AD,T

5100

25

32

35

12

30

12

—

16

—

6120

35

45

52

17

62

20

—

25

—

5440

17

25

42

12

35

12

—

9

10

WSC120AD,T

6800

27

37

65

17

75

20

—

14

17

8160

40

50

85

22

87

25

—

20

26

Notes:

1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop

should be considered when utilizing optional 50 mm (2 inch) pleated filters.

2. OA = Outside Air and RA = Return Air

3. Nominal kW ratings at 380 V

Table PD-22a - Static Pressure Drops Through Accessories - (Inches of Water Column)

Econimizer with

Electric Heater

OA/RA Dampers

2

Accessory (kW)

3

Unit

Airflow

Standard

Pleated Filters

100% OA

100% RA

100% OA

100% RA

7-9

10-27

37-40

Model No.

(CFM)

Filters

1

50 mm (2 inch)

Downflow

Horizontal

1600

0.10

0.15

0.12

0.04

0.12

0.01

0.045

0.053

—

WSC060AD,T

2000

0.15

0.22

0.18

0.07

0.18

0.02

0.070

0.083

—

2400

0.22

0.29

0.26

0.10

0.26

0.04

0.100

0.120

—

1920

0.04

0.07

0.10

0.01

0.06

0.02

—

0.021

—

WSC072AD,T

2400

0.06

0.09

0.11

0.02

0.08

0.02

—

0.034

—

2880

0.09

0.12

0.13

0.04

0.10

0.04

—

0.052

—

2400

0.06

0.09

0.11

0.02

0.08

0.02

—

0.034

—

WSC090AD,T

3000

0.10

0.13

0.14

0.05

0.12

0.05

—

0.063

—

3600

0.14

0.18

0.21

0.07

0.25

0.08

—

0.102

—

3200

0.07

0.10

0.17

0.05

0.14

0.05

—

0.036

0.042

WSC120AD,T

4000

0.11

0.15

0.26

0.07

0.30

0.08

—

0.056

0.070

4800

0.16

0.20

0.34

0.09

0.35

0.10

—

0.081

0.106

Notes:

1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop

should be considered when utilizing optional 50 mm (2 inch) pleated filters.

2. OA = Outside Air and RA = Return Air

3. Nominal kW ratings at 380 V

Table PD-23 — Electric Heater Voltage Correction

Factors (Apply to Auxiliary Heat
Capacity)

Nominal

Distribution

Capacity

Voltage

Voltage

Multipiler

200

200

1.00

380

0.84

415

400

0.93

415

1.00