Performance data – Trane WSC060-120 User Manual

Page 33

Advertising
background image

PKGP-PRC004-EN

33

Performance
Data

Table PD-26 — Electric Heater Temperature Rise Correction Factors

% Variation From Nominal Airflow – 20

– 15

– 10

– 5

0

+ 5

+ 10

+ 15

+ 20

Temperature Rise Multiplier

1.25

1.17

1.11

1.05

1

0.95

0.91

0.87

0.83

Table PD-25 — Air Temperature Rise Across Electric Heaters (Degrees C)

5 Ton

6 Ton

7.5 Ton

10 Ton

3400 M

3

/H

4100 M

3

/H

5100 M

3

/H

6800 M

3

/H

kW

Stages

WSC060AD, T

WSC072AD, T

WSC090AD, T

WSC120AD, T

7.5

2

6.6

—

—

—

8.3

2

7.3

—

—

—

9.0

2

7.9

—

—

—

10.9

2

9.6

—

—

—

11.3

1

—

8.3

6.6

—

12.1

2

10.6

—

—

—

12.5

1

—

9.1

7.3

—

13.0

2

11.4

—

—

—

13.5

1

—

9.9

7.9

—

14.4

2

12.6

—

—

—

16.0

2

14.0

—

—

—

16.9

2

—

12.4

9.9

7.4

17.2

2

15.1

—

—

—

18.8

2

—

13.8

11.0

8.3

20.2

2

—

14.8

11.8

8.9

22.6

2

—

16.5

13.2

9.9

25.0

2

—

18.3

14.6

11.0

26.9

2

—

19.7

15.7

11.8

33.9

2

—

—

—

14.9

37.5

2

—

—

—

16.5

40.4

2

—

—

—

17.7

Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (C

0

) across Elect Htr = (kW x 2985) / (M

3

/H)

Table PD-25a — Air Temperature Rise Across Electric Heaters (Degrees F)

5 Ton

6 Ton

7.5 Ton

10 Ton

2000 CFM

2400 CFM

3000 CFM

4000 CFM

kW

Stages

WSC060AD, T

WSC072AD, T

WSC090AD, T

WSC120AD, T

7.5

2

11.9

—

—

—

8.3

2

13.1

—

—

—

9.0

2

14.2

—

—

—

10.9

2

17.2

—

—

—

11.3

1

—

14.9

11.9

—

12.1

2

19.1

—

—

—

12.5

1

—

16.5

13.2

—

13.0

2

20.5

—

—

—

13.5

1

—

17.8

14.2

—

14.4

2

22.8

—

—

—

16.0

2

25.3

—

—

—

16.9

2

—

22.3

17.8

13.4

17.2

2

27.2

—

—

—

18.8

2

—

24.8

19.8

14.9

20.2

2

—

26.6

21.3

16.0

22.6

2

—

29.8

23.8

17.9

25.0

2

—

32.9

26.3

19.8

26.9

2

—

35.4

28.3

21.3

33.9

2

—

—

—

26.8

37.5

2

—

—

—

29.6

40.4

2

—

—

—

31.9

NOTE:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (F

0

) across Elect Htr = (kW x 3414) / ( 1.08 x CFM)

Advertising