Condensate Drain Piping

-

The drain hose should run

straight down the wall to a
level where the runoff will not
stain the wall.

-

There should be no traps.

Avoid putting the end of the
hose in water.

-

To conveniently drain the

system, the drain hose must
slant downward, with a slope
of at least 1 : 50 to prevent
leakage. Figure 23 shows the
unit in the floor mounted
position.

-

When the drain hose is placed

in the room, insulate the hose
with foam polyethylene to
avoid damage to the ceiling or
furniture.

-

After completing installation of

refrigerant lines, wiring and
drain connections, bind the
tubing, wiring and drain hose
(check if local codes permit
binding) into a bundle by using
tape at 100 or 200 mm (4" to
8") intervals. Make sure the
drain hose is at the bottom of
the bundle (Figure 24).

Figure 24

Figure 23

Drain hose

Indoor unit

Slant

Drain hose