Phase ups specifications addendum—50kva & above, Español 7, Torque specifications – Tripp Lite 220/380V User Manual

Page 45: Recommended cable sizes, Floor weight loading table

Advertising
background image

1

Torque Specifications

SU50K3/3PM, SU50K3/3INTPM:

• 150A Terminal Blocks: 61 kgf-cm (4.4 ft-lb)

• 200A Terminal Blocks: 102 kgf-cm (7.4 ft-lb)

SU80K3/3PM, SU80K3/3INTPM, SU100K3/3PM,
SU100K3/3INTPM, SU120K3/3PM:

• 200A Terminal Blocks: 102 kgf-cm (7.4 ft-lb)

• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)

SU120K3/3INTPM:

• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)

• 200A Terminal Blocks (w/M10 screw): 102 kgf-cm (7.4 ft-lb)

SU160K3/3PM, SU160K3/3INTPM, SU200K3/3PM,
SU200K3/3INTPM:

• Bus Bar (w/M8 screw): 110 kgf-cm (8.0 ft-lb)

Recommended Cable Sizes

UPS Power Module

SU50K SU80K SU100K

SU120K

SU160K SU200K

SU50K

SU80K

SU100K

SU120K SU160K

SU200K

Model

3/3PM

3/3PM

3/3PM

3/3PM

3/3PM

3/3PM

3/3INTPM

3/3INTPM

3/3INTPM

3/3INTPM 3/3INTPM

3/3INTPM

UPS System Capacity (kVA)

50

80

100

120

160

200

50

80

100

120

160

200

Input Circuit Breaker (A)

100

150

175

225

300

350

125

200

225

300

350

500

Input Cable (AWG)

2

1/0

3/0

4/0

250

Kcmil*

400

Kcmil*

1

3/0

3/0

4/0

250

Kcmil*

500

Kcmil*

Input Cable (mm

2

)

22

50

70

95

120

185

38

70

125

125

185

80 x 2

Reserve Input Circuit Breaker (A) 75

125

150

175

250

300

100

150

200

225

300

400

Reserve Input Cable (AWG)

6

2

1

1/0

3/0

250

Kcmil*

4

1

3/0

4/0

250

Kcmil*

500

Kcmil*

Reserve Input Cable (mm

2

)

10

25

35

50

70

120

22

38

80

100

38 x 2

80 x 2

Output Circuit Breaker (A)

75

125

150

175

250

300

100

150

200

225

300

400

Output Cable (AWG)

6

2

1

1/0

3/0

250

Kcmil*

4

1

3/0

4/0

250

Kcmil*

500

Kcmil*

Output Cable (mm

2

)

10

25

35

50

70

120

22

38

80

100

38 x 2

80 x 2

See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Cable Size Information. *Kcmil=MCM

1111 W. 35th Street

Chicago, IL 60609 USA

(773) 869-1234 • www.tripplite.com

Copyright © 2007 Tripp Lite. All rights reserved. The policy of Tripp Lite is one of continuous improvement. Specifications and diagrams are subject to change without notice.

3-Phase UPS Specifications

Addendum—50kVA & Above

Español

7

Floor Weight Loading Table

UPS Power Module

SU50K

SU80K

SU100K SU120K

SU160K

SU200K

SU50K

SU80K

SU100K SU120K

SU160K SU200K

Model

3/3PM

3/3PM

3/3PM

3/3PM

3/3PM

3/3PM

3/3INTPM

3/3INTPM

3/3INTPM 3/3INTPM

3/3INTPM 3/3INTPM

UPS System Capacity (kVA)

50

80

100

120

160

200

50

80

100

120

160

200

Weight (lb)

1276

1540

2040

2280

2550

2760

1012

1155

1543

1642

2315

2392

Weight (kg)

580

700

1020

1140

1275

1380

460

525

700

745

1050

1085

Weight Loading (lb/in

2

)

1.716

1.495

1.32

1.48

1.65

1.79

1.361

1.554

1.50

1.60

1.50

1.55

Weight Loading (kg/m

2

)

1208

1054

1024

1145

1280

1386

958

1094

1054

1122

1054

1089

See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Weight Loading Information.