Performance
Adjustment
Factors

Wet Bulb Temperature

Btu Per Lb.

40

15.23

41

15.70

42

16.17

43

16.66

44

17.15

45

17.65

46

18.16

47

18.68

48

19.21

49

19.75

50

20.30

51

20.86

52

21.44

53

22.02

54

22.62

55

23.22

56

23.84

57

24.48

58

25.12

59

25.78

60

26.46

61

27.15

62

27.85

63

28.57

64

29.31

65

30.06

66

30.83

67

31.62

68

32.42

69

33.25

70

34.09

71

34.95

72

35.83

73

36.74

74

37.66

75

38.61

Table PAF-2 — Cooling Capacity Altitude Correction Factors

Altitude (Ft.)

Sea Level

1000

2000

3000

4000

5000

6000

7000

Cooling Capacity

Multiplier

1.00

0.99

0.99

0.98

0.97

0.96

0.95

0.94

KW Correction

Multiplier
(Compressors)

1.00

1.01

1.02

1.03

1.04

1.05

1.06

1.07

SHR Correction

Multiplier

1.00

.98

.95

.93

.91

.89

.87

.85

Maximum

Condenser
Ambient

115 F

114 F

113 F

112 F

111 F

110 F

109 F

108 F

Note:
SHR = Sensible Heat Ratio

Figure PAF-1 — Air Density Ratios

Altitude/Temperature Correction

Air Density
Ratio (Density
at New
Air Density)
Condition/Std.

Rooftop Leaving Air Temperature (degrees F)

Table PAF-3 — Gas Heating Capacity Altitude Correction Factors

Altitude (Ft.)

Sea Level

2001

2501

3501

4501

5501

6501

To 2000

To 2500

To 3500

To 4500

To 5500

To 6500

To 7500

Capacity

Multiplier

1.00

.92

.88

.84

.80

.76

.72

Note:
Correction factors are per AGA Std 221.30 — 1964, Part VI, 6.12. Local codes may supersede.

Table PAF-1 — Enthalpy of Saturated AIR