OPERATION

MANUAL CLOSING (Manual Spring-Operated
U and L Types):

1. Check to make sure that the On-Off

indicator shows OFF (green).

2. Turn the closing handle clockwise. The

breaker will close (On-Off indicator changes
to ON) after the handle is turned
approximately 75

°.

NOTE

If the handle is turned in small
increments, the closing spring will
store the energy from the handle
action and the circuit breaker will
close before 75

° of rotation.

3. Release the handle, and it will return to its

initial position.

MANUAL OPENING (All Types):

1. Push the trip lever in the direction of the

arrow (Fig. 25).

2. The On-Off indicator changes to OFF

(green).

ELECTRICAL OPERATION

The flow chart shown in Fig. 27 illustrates the
sequence of electrical operation of the MU and
ML type circuit breakers.

Refer to Fig. 26 and the circuit breaker
schematics shown in Fig. 28 through Fig. 31 for
determining external control circuit connections
to the circuit breaker.

Fig. 25 Manually Opening Breaker

SYMBOL

DESCRIPTION

M

Motor

TC

Voltage Trip Coil

UV

Undervoltage Trip Coil

a1 to a6

Auxiliary Contacts (N.O.)

b1 to b6

Auxiliary Contacts (N.C.)

X

Control Relay

X-a

Control Relay Contact (N.O.)

X-b

Control Relay Contact (N.C.)

Y

Auxiliary Relay

Y-a

Auxiliary Relay Contact (N.O.)

Y-b

Auxiliary Relay Contact (N.C.)

LS1 to LS3

Limit Switches

R1 to R4

Resistors

REC

Rectifier

D

Diode

C

Capacitor

SP

Surge Protector

RL

Red Lamp

GL

Green Lamp

Fig. 26 Legend for Schematics