Maintenance page 27 – Toshiba HV6AS User Manual

Page 31

Advertising
background image

MAINTENANCE

Page 27

Table 2 Check Points for Periodic Inspection

Check Point

Check Item

Check Method

Criteria

Disposition

Operating
Mechanism

Loose bolts,
nuts or screws

Tighten using
screwdriver or
wrench.

Make sure all bolts, nuts
and screws are tight.

Tighten if loose.
See Table 1 for
tightening torques.

Dust or foreign
matter inside

Visual
inspection.

The circuit breaker
should be clean and
contain no foreign matter.

Wipe with a clean
dry cloth.

Indicator
operation

Visual
inspection.

Make sure the number of
operations is correctly
displayed.

Check the cause
and repair.

Warpage

Visual
inspection.

There should be no
warpage or missing
parts.

Check the cause
and repair.

Smooth
operation

Manual
operation.
Visual
inspection or
touch. Check
lubrication.

Make sure moving parts
operate smoothly.

Apply a small
amount of
lubrication.

Main Circuit

Discoloration
due to heat
from conducting
parts

Visual
inspection.

Make sure there is no
discoloration.

Check the cause
and repair. Tighten
connections to circuit
breaker. See Table
1 for tightening
torques.

Loose bolts,
nuts or screws

Tighten using a
wrench.

Make sure all bolts, nuts
and screws are tight.

See Table 1 for
tightening torques.

Dust on surface
of vacuum
interrupter

Visual
inspection.

Make sure there is no
dust on the surface.

Wipe with a clean,
dry cloth.

Insulator

Dust, foreign
matter or
damage

Visual
inspection.

Make sure there is no
dust, foreign matter or
breakage.

Wipe with a clean,
dry cloth. If
damaged, contact
Toshiba.

Advertising