Meets or Exceeds

Your Specifications

HX7 Standard Specifications

Item

Voltage Class

460 V

Maximum HP

60

75

100

125

150

200

250

300 350

400

500

600

700

800

Drive Rating (A)

77

96

124

156

190

240

302

370 450

480

628

740

900

960

Dimensions (in.)

100 H x 30 W x 24 D

100 H x 42 W x 24 D

100 H x 76 W x 24 D

Power Requirements

Output Frequency

0 to 299 Hz

Main Circuit

Three-Phase, 460 V Input Auto-Transformer, 18-Pulse Design with Circuit Breaker, IGBT Output

Control Power

DC Bus Control Power

Tolerance

Voltage: ±10%; Frequency: ±2%

Control Specifications

Control Method

Sine Wave PWM System; Flux-Field Current Vector Control

V/Hz Control

Constant Torque, Variable Torque, Open-Loop Vector, Auto or Manual Torque Boost, Five-Point V/Hz Custom Curves

Overload Rating

120% for 60 Seconds; 100% Continuous

Frequency Setting

Rotary Encoder Integrated into EOI, 0 to 10 V, ±10 V, 4 to 20 mA, Binary Input, Motorized Potentiometer Input

Frequency Precision

Analog Input: ±0.2% of Maximum Output Frequency; Digital Input: ±0.01% of Maximum Output Frequency

Frequency Resolution

Panel Operation: 0.01 Hz; Analog Input 10 to 12-Bit A to D Converter: 0.1 Hz

Acceleration/Deceleration

0.1 to 6000 Seconds

Speed Regulation

Up to 0.1%; 60:1 Speed Range

Torque Regulation

10% Regulation; Less than 2% Ripple from 50 to 100% Range

Set Point Control (PID)

Proportional Gain, Integral Gain, Feedback Setting Upper/Lower Deviation Limits; Feedback Source Delay Filter,

Feedback Setting Differential Gain

Analog Inputs

Four Programmable: One 4 to 20 mA, One 0 to 10 V, One -10 to +10 V, One 1 to 10 kΩ Potentiometer Connection

Analog Outputs

Two Programmable to 31 Functions

Input Terminals

Eight Discrete Input Terminals Programmable to 67 Functions; Expandable to N-Value

Output Contacts

Three Output Terminals Programmable to 52 Functions; Form-C Contacts Rated 250 VAC, Two Amps Inductive

Signal Isolation

Available Three-Channel Signal Isolation for AM/FM Outputs and II Terminal Input, Rated at 750 V

Control Board

Communication Ports

RS232/485 and TTL Ports Standard

Data Transmission

Profibus, DeviceNet, Modbus RTU, Modbus+, Metasys, Ethernet (Some Devices External)

Main Protective

Functions

Current Limit, Overcurrent, Overvoltage, Undervoltage, Load-Side Short Circuit, Load-Side Ground Fault, Armature Short,

Overtorque, ASD Overload, Motor Overload, Heatsink Overheat, Open-Output Phase, Loss of Feedback, CPU Error,

Communications Error

Soft Stall

Automatic Load-Reduction Control During Overload

Retry

Can Automatically Clear Fault upon Trip; Programmable to 10 Retries with up to 10 Seconds Between Each Retry

Restart

Able to Restart to Catch a Spinning Motor

Interface

LCD/EOI (Liquid Crystal

Display)/(Electronic

Operator Interface)

128 x 64 Pixel Backlit LCD; Able to Display Multiple Parameters on One Screen; Keypad Operable from External Power

Source; Flash-Upgradeable Software Includes Multi-Function Rotary Encoder

LED Indicators

Run (Red)/Stop (Green), Remote/Local (Green), DC Bus Charge Indication (Red)

Keypad

Local/Remote, Monitor/Program, Run, Enter, ESC, Stop/Reset, Up, Down

Monitoring

Main Display Shows Two Monitored Items Continuously or Scrolls up to 40 Items

Selectable Display Units

User-Selectable and Configurable, Along with Scaling Factor Multiplier; Voltage Display Selectable Between Volts or

Percentage; Current Display Selectable Between Amps or Percentage

EOI Communication Ports

RS232/485 and TTL Ports Standard

Remote Mounting

Remote-Mountable up to 1000 Feet

Construction

Enclosure

NEMA 1, IP20, Gasketed and Filtered

Panel Construction

Free-Standing, Front-Access Maintenance, Top/Bottom Cable Access

Cooling

Force-Air Cooled; Top-Mounted Fans Removable During Shipment or Installation

Color

ANSI-61 Gray

Ambient Conditions

Ambient Temperature

0 to 40°C (32 to 104°F)

Humidity

Maximum 95% (Non-Condensing)

Altitude

1000 Meters (3300 Feet) Above Sea Level Without Derating

Installation

Indoor; Keep Out of Direct Sunlight; Protect from Corrosive and/or Explosive Gases

Standards

Electrical Compliance

NEC, ANSI