Configuration

Set Configuration DIP Switches

Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger
operation depending on your application. Warning: Make sure the unit is turned OFF before changing DIP Switch settings.

208 V

230 V

60 Hz

50 Hz

Faster

Slower

Select Line Voltage - REQUIRED

Voltage Switch

Position

208 VAC

Up

230 VAC

Down (factory setting)

4

Select Frequency - REQUIRED

Frequency Switch

Position

60 Hz

Up

50 Hz

Down (factory setting)

3

Select Line Connect Relay Transfer Time - OPTIONAL

Transfer Time

Switch Position

1/2 Cycle Transfer Time Up

1 Cycle Transfer Time

Down (factory setting)

2

Not Used

1

BATTERY

HIGH

MED
LOW

OPERATION

LINE

INV

LOAD

REMOTE

CONTROL

CONFIGURATION DIP SWITCHES

(SEE MANUAL OR TOP OF UNIT FOR INSTRUCTIONS)

1 2 3 4

5 6 7 8

9 10 11 12

1 2 3 4

1 2 3 4

1 2 3 4

Note: If you will use the Inverter/Charger to
support computers or other sensitive
electronic equipment loads, set the transfer
time to ½ cycle (switch #2 UP) to ensure
uninterrupted operation when the
Inverter/Charger transfers to battery power.

“Reset”

“Equalize”

Low Charge Amp

High Charge Amp

1

Select Equalize Battery Charge - OPTIONAL

Battery Charge

Switch Position

Reset

Up (factory setting)

Equalize

Down

(momentarily)

Battery Charger

Switch Position

Low Charge Amps (23A)

Up (factory setting)

High Charge Amps (90A)

Down

6

Select Battery Charger Amp Setting

5

7

8

9

This DIP Switch is momentarily engaged to begin the process of
equalizing the charge state of your battery’s cells by time-limited
overcharge of all cells. This can extend the useful life of certain types
of batteries; consult with your battery’s manufacturer to determine if
your batteries could benefit from this process. The charge equalization
process is automatic; once started, it can only be stopped by removing
the input power.

Setting Procedure
• Move to “Equalize” (DOWN) postition for three seconds.
• Move to “Reset” (UP) postition and leave it there. This is the factory default setting.

CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery charge
equalization should only be performed in strict accordance with the battery manufacturer’s instructions
and specifications.

CAUTION: When switching to the High Charge Amp setting, the user
must ensure that the amp hour capacity of their battery system exceeds
the amperage of the High Charge Amp setting or the batteries may be
damaged or degraded.

Not Used

5 6 7 8

5 6 7 8

Advertising