ADJUSTABLE SPEED DRIVES MOTORS CONTROLS UPS INSTRUMENTATION PLC

TOSHIBA INTERNATIONAL CORPORATION

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041

Tel 713/466-0277 Fax 713/466-8773

US 800/231-1412 Canada 800/872-2192 Mexico 001/800/527-1204

www.tic.toshiba.com

Copyright 10/2005 Toshiba International Corporation

Available Through:

Model Number

UF1A1A020C6

2.4 kVA

Capacity

2000VA(1400W)

Topology

True on-line, double conversion, IGBT PWM, with input power factor correction

Input

Input Voltage

Single phase 120VAC, +20% to -50%

Input Frequency

30 to 70 Hz (50/60 Hz selectable)

Input Power Factor

Approximate unity 1.0

Output

Output Voltage

Single phase 120VAC, +/- 3%, steady state

Output Frequency

50/60 Hz (+/-0.5% in free run mode, line sync +/-3%)

Output Wave Form

Sine wave, zero transfer time

Rated Load Power Factor

0.7

Rated Output Current

16.7A

Inverter Overload Capacity

125% for one minute, 150% for 30 seconds

Crest Factor

2.5 at full load

Battery Rack

Model Number UF1-BR-087

12V– 7Ah, flame retardant, sealed lead acid (VRLA)

Battery Backup Time

10 minutes (full load) 30 minutes (half load)

Configuration

2 strings @ 4 x 12 VDC (48VDC)

Line Cord

5-20P (6 feet)

1-5-30P

Receptacles

(5)5-15R

1 (4) 5-15 (1) 5-20R

Environment

Operating Temperature

0 to 40 degrees C (32 to 104 degrees F)

Altitude

Up to 1000m (3000 ft) above sea level

Efficiency AC/DC/AC

> 86%

Dimensions

Size

22” x 19” x 3.5” (L x W x H) per unit UPS-2U Battery-2U

Weight

30 lbs. (UPS) 56 lbs. (Battery)

Warranty

3 Year on electronics / 2 Years full on Battery

(see Toshiba warranty

policy for full details)

1700 Series 2 kVA Rackmount UPS

UPS

Battery

RemotEyeII

®

SNMP/WEB monitor

(slide-in option)