Modbus module operation, Modbus commands – Toshiba PROSEC T2 Series User Manual
Page 12
 
Page 6
5. Modbus Module Operation
5.1. Modbus Commands
 
When a MODBUS command is used, the Modbus module translates it to the 
corresponding T2 register access protocol. 
 
 
MODBUS FUNCTION CODE
T2 COMMAND
01 Read Coil Status
DR Read Device/Register
02 Read Input Status
DR Read Device/Register
03 Read Holding Register
DR Read Device/Register
04 Read Input Register
DR Read Device/register
05 Force Single Coil
DW Write Device Register
06 Force Single Register
DW Write Device/Register
08 Loop Back Diagnostic test
**** Not Supported by EX10-MML11
15 Force Multiple Coils
DW Write Device/register
16 Preset Multiple Registers
DW Write Device/register
 
 
For more information on the Modbus protocol, please refer to the Modbus Protocol Reference 
Guide, see 
Additional References
.
 
 
For more information on the T2 register access protocol, please refer to the Computer Link 
Function Operation Manual, see 
Additional References
.