Restricted registers – Toshiba PROSEC T2 Series User Manual
Page 14
 
Page 8
Modbus – T2 Address mapping Example: 
 
 
 
 
 
 
 
 
 
 
 
Modbus Address
T2 Address
T2 Data Type
30000 XW000
Input
Register
40001 YW001
Output
Register
44352 D0000
Data
Register
 
 
Note: When dealing with I/O registers, make sure that the Modbus master is attempting to 
access only the I/O points that physically exist in the T2 system. For example, Holding 
Register 0 (40000) does not exist in the above example because there is no YW000 in the T2 
system. In the above system, only have Holding Register 1 (40001) exists. 
 
 
 
5.3. Restricted Registers
Registers D1406 to D1535 are reserved for “raw” data transmission with the EC300 loop 
controllers on the ECBUS network. These registers are not available when the EX10-MML11 
is used as a Modbus slave module. Do not use these registers. 
T2E CPU
Modbus Module
Input module 
 (XW000) 
Output Module 
 (YW001) 
In this example, the T2 is being used 
As a Modbus Remote Terminal Unit 
slave. A Modbus master can access 
The I/O or data registers in the T2. 
See the following table for a Modbus to 
T2 address mapping example.